Baldor AE11 Single Phase Power Connections, 9 Single Phase Output Power Connections, GND Load

Models: AE8 AE25 AE10 AE11

1 74
Download 74 pages 35.07 Kb
Page 24
Image 24
Figure 3-9 Single Phase Output Power Connections

AE25 Electrical Connections Applies only to AE25 Enclosed Series Generators

Single Phase Power Connections

The generator has a 240V single phase AC output. These connections are made at the power terminal box shown in Figure 3-9.

Figure 3-9 Single Phase Output Power Connections

AE25 with Enclosure (Natural Gas or LPG)

GND

Load

N

L1

L2

 

 

 

L1 to N

120VAC

 

Customer

L2 to N

120VAC

 

L1 to L2

240VAC

AC Output Connections

(to Transfer Switch)

Remote Start and Battery Charger Connections

Figure 3-10shows the connections for the battery charger and the remote start contacts of the transfer switch. When the Remote Start Switch is closed, the generator will start. The unit will remain running until this connection is opened. When the Remote Start Switch is opened, the control circuits allow the engine to run for approximately 60−90 seconds before it shuts off. This time delay allows the engine to run unloaded to cool down before stopping.

Figure 3-10 Remote Start & Battery Connections

AE25 with Enclosure (Natural Gas or LPG)

R2 R1

TB1

16AWG

Twisted Pair Wire

 

 

 

 

Customer Provided Optional Equipment

 

 

 

Out+

Battery

 

 

 

Out−

 

 

 

Charger

 

+

 

Remote Start Switch

 

 

 

 

 

 

(Close to Start)

Battery

 

To 120VAC

(Shore Power)

3-12 Receiving & Installation

MN2415

Page 24
Image 24
Baldor AE11 Single Phase Power Connections, 9 Single Phase Output Power Connections, 10 Remote Start & Battery Connections