To 120VAC (Shore Power)
Out−
Battery
Charger
16AWG Customer Provided Optional Equipment
Twisted Pair WireRemote Start Switch (Close to Start)
Out+
Figure 3-8 shows the connections for the battery charger and the remote start contacts of the transfer switch. When the Remote Start Switch is closed, the generator will start. The unit will remain running until this connection is opened. When the Remote Start Switch is opened, the control circuits allow the engine to run for approximately 60−90 seconds before it shuts off. This time delay allows the engine to run unloaded to cool down before stopping.
Figure 3-8 Remote Start & Battery Connections
AE11 Electrical Connections Applies only to AE11 Enclosed Series Generators
Single Phase Power Connections
The generator has a 240V single phase AC output. These connections are made at the power terminal box shown in Figure
Figure 3-7 Single Phase Output Power Connections
AE11 with Enclosure
TBP
| L1 | L1 |
| Customer |
| L2 | L2 |
| |
| AC Output Connections | |||
Generator | L3 |
|
| (to Transfer Switch) |
Output | N | N |
|
|
(Jumpered) | N |
|
|
|
| G |
| L1 to N | 120VAC |
(Jumpered) | G |
| L2 to N | 120VAC |
| L1 to L2 | 240VAC | ||
|
|
|
BW0459D
Remote Start and Battery Charger Connections
AE11
with Enclosure
TBP
L1
N
G
Remote Start
Remote Start
Fuel Jumper
Fuel Jumper
Fuel Jumper
IN = Natural Gas
OUT = LPG
Note: Remove Fuel Jumper
BW0459D
if LP Gas is used.
+−
Battery
MN2415 | Receiving & Installation |