AE11 Operating Procedures

The AE11 engine controller is programmable and it’s internal workings is more complex than the other AE series generators.

Auto Start Operation

This mode is activated by pressing the Auto pushbutton, see Figure 4-2. An LED indicator beside the button lights in Auto mode. The start sequence is initiated when the remote start input from the transfer switch or other device is activated. To prevent a false remote start, the Start Delay timer is initiated. If the Remote Start signal is removed during the Start Delay timer, the unit returns to stand−by. After the Start Delay, if the pre−heat output option is selected, the pre−heat timer is starts, and the corresponding auxiliary output (if configured) will energize.

After these delays, the Fuel Solenoid is energized, then one second later, the Starter Motor is engaged. The engine is cranked for a 10−second period. If the engine fails to start, the starter motor is disengaged for a 10−second rest period. Should this sequence continue beyond the 3 starting attempts, the start sequence will be terminated and Fail to Start fault will be illuminated.

When the engine starts, the starter motor is disengaged and locked out at 20 Hz measured at the Alternator output. (Rising oil pressure can also be used to disconnect the starter motor, however it cannot be used for under speed or over speed detection).

When the starter motor has disengaged, the Safety On timer starts. This timer is preset to 12 seconds and allows engine speed, Oil Pressure, High Engine Temperature, Under−speed, Charge Fail and Auxiliary fault inputs to stabilize without triggering a fault. Once the engine is running, the Warm Up timer starts (if selected). This allows the engine to stabilize before the load is switched on. After the Warm Up delay, the AC output is switched on to operate the load. When the Remote Start signal is removed, the Stop Delay timer is initiated. After which the Load Transfer output (if configured) is deactivated, and the Cool Down Period is initiated. After the Cool Down Period has elapsed, the Fuel Solenoid is de−energized, bringing the generator to a stop.

Manual Operation There is no “Start Delay” in Manual Run.

This mode is activated by pressing the Manual Run pushbutton, see Figure 4-2. If the pre−heat output option is selected, the pre−heat timer is starts, and the corresponding auxiliary output (if configured) will energize. After this delay, the Fuel Solenoid is energized, then one second later, the Starter Motor is engaged. The engine is cranked for a 10−second period. If the engine fails to start, the starter motor is disengaged for a 10−second rest period. Should this sequence continue beyond the 3 starting attempts, the start sequence will be terminated and Fail to Start fault will be illuminated. When the engine starts, the starter motor is disengaged and locked out at 20 Hz measured at the Alternator output. (Rising oil pressure can also be used to disconnect the starter motor, however it cannot be used for under speed or over speed detection).

When the starter motor has disengaged, the Safety On timer starts. This timer is preset to 12 seconds and allows engine speed, Oil Pressure, High Engine Temperature, Under−speed, Charge Fail and Auxiliary fault inputs to stabilize without triggering a fault. Once the engine is running, the Warm Up timer starts (if selected). This allows the engine to stabilize before the load is switched on. After the Warm Up delay, the AC output is switched on to operate the load. The generator will continue to run until the “Stop” or “Auto Start” mode is selected.

If Auto mode is selected, the Remote Stop Delay Timer starts. After this delay, the Fuel Solenoid is de−energized, to stop the generator.

Selecting Stop de−energizes the Fuel Solenoid is de−energized, to stop the generator.

Warnings and Shutdowns

Warnings

Warnings are used to warn the operator of a problem fault. Battery Charge Failure, if the module does not detect a voltage from engine mounted alternator, the lamp will illuminate. (Either 8 Volts or 16 Volts depending on the configuration of Nominal DC Voltage). Inputs 1 and 2 can be configured as warnings or shutdowns. The lamp will be illuminated when the input is active.

Shutdowns

Shutdowns are latching and stop the Generator. The alarm must be cleared, and the fault removed to reset the module. In the event of a shutdown the appropriate lamp is illuminated. The alarm condition must be corrected before a reset will take place. If the alarm condition remains it is not possible to reset the unit (except faults that occur during the “Safety On timer” period. These are delayed alarms, like oil pressure is low with the engine at rest).

Inputs 1 and 2 can be configured as warnings or shutdowns. The relevant lamp is illuminated when the input is active.

4-4 Operation

MN2415

Page 34
Image 34
Baldor AE25, AE10, AE8 manual AE11 Operating Procedures, Auto Start Operation, Shutdowns

AE8, AE25, AE10, AE11 specifications

Baldor Electric Company has long been a trusted name in the manufacturing of electric motors and drives. Among their impressive lineup of products, the AE series, which includes the AE11, AE25, AE10, and AE8 models, stands out for their innovative features and robust performance, making them suitable for a variety of industrial applications.

The Baldor AE11 is designed with high efficiency in mind, ensuring that it consumes less energy while delivering optimal performance. This motor features a robust design that enhances durability and reliability, making it ideal for heavy-duty applications. The AE11 also incorporates advanced thermal management technology, ensuring that the motor remains cool even during prolonged use. Its compact size allows for easier integration in tight spaces, making it a versatile choice for many machinery types.

The AE25 model takes performance a step further with its enhanced power output and torque capabilities. This model is built for demanding environments and is engineered to reduce vibration and noise, providing a smoother operational experience. The AE25 also features built-in thermal protection, which automatically shuts down the motor in case of overheating, thereby safeguarding the equipment and reducing maintenance costs.

For those needing a more compact solution, the AE10 offers a balance of power and size. This electric motor is designed with a lightweight yet sturdy build, providing a perfect fit for smaller machines without sacrificing performance. The AE10 is equipped with high-energy efficiency ratings, contributing to lower operational costs and reduced environmental impact. Additionally, it supports various mounting options, enhancing its adaptability for different applications.

Lastly, the AE8 model is a true powerhouse for applications where space is at a premium. It features a minimalist design while still delivering reliable performance. The AE8 is optimized for energy efficiency, boasting a streamlined motor design that minimizes wasted energy. With its quiet operation and low maintenance requirements, this model is ideal for environments where noise reduction is essential.

In summary, the Baldor AE series—including the AE11, AE25, AE10, and AE8—shows a real commitment to efficiency, durability, and versatility. Each model is tailored to meet specific industry needs, whether for demanding heavy-duty applications or compact, energy-efficient setups. With their innovative technologies and engineering excellence, Baldor motors continue to set the standard in the electric motor industry.