Caution: | To prevent equipment damage, be certain that the input power | |
| has correctly sized protective devices installed as well as a power | |
| disconnect. |
|
Caution: | Avoid locating the control immediately above or beside heat | |
| generating equipment, or directly below water or steam pipes. | |
Caution: | Avoid locating the control in the vicinity of corrosive substances | |
| or vapors, metal particles and dust. | |
Caution: | Suitable for use on a circuit capable of delivering not more than | |
| the RMS symmetrical short circuit amperes listed here at rated | |
| voltage. | RMS Symmetrical Amperes |
| Horsepower | |
| 5,000 | |
| 10,000 | |
| 18,000 | |
| 30,000 | |
| 42,000 | |
Caution: | Baldor recommends not using “Grounded Leg Delta” transformer | |
| power leads that may create ground loops and degrade system | |
| performance. Instead, we recommend using a four wire Wye. | |
Caution: | Logic signals are interruptible signals; these signals are removed | |
| when power is removed from the drive. | |
Caution: | The safe integration of the driver into a machine system is the | |
| responsibility of the machine designer. Be sure to comply with | |
| the local safety requirements at the place where the machine is to | |
| be used. In Europe this is the Machinery Directive, the | |
| ElectroMagnetic Compatibility Directive and the Low Voltage | |
| Directive. In the United States this is the National Electrical code | |
| and local codes. |
|
Caution: | Controls must be installed inside an electrical cabinet that | |
| provides environmental control and protection. Installation | |
| information for the drive is provided in this manual. Motors and | |
| controlling devices that connect to the driver should have | |
| specifications compatible to the drive. | |
Caution: | Do not tin (solder) exposed wires. Solder contracts over time and | |
| may cause loose connections. | |
Caution: | Electrical components can be damaged by static electricity. Use | |
| ESD | |
| control. |
|
MN735 |