Table 4-1 Parameter Definitions Continued
Display | Parameter | Description | Range | Factory |
|
|
|
| Setting |
| RELAY INVERT | True =Inverts the input signal. | 0= False | 0 |
|
|
| 1= True |
|
| RELAY VALUE | The output signal that represents the OP31 | 0= False | 0 |
| ~ | choice. | 1= True |
|
|
| SET::TRIP Menu |
|
|
| DISABLE LOOP | Disables LOST I LOOP trip | 0= Trip Enabled | 1 |
|
|
| 1= Trip Disabled |
|
| AIN2 | Disables the overload trip (Terminal 3) | 0= Trip Enabled | 0 |
| OVERLOAD |
| 1= Trip Disabled |
|
| DISABLE | Disables STALL trip | 0= Trip Enabled | 0 |
| STALL |
| 1= Trip Disabled |
|
| DISABLE | Disables the motor thermistor trip | 0= Trip Enabled | 0 |
| MOTOR |
| 1= Trip Disabled |
|
| OVERTEMP |
|
|
|
|
| SET::SETP Menu |
|
|
| Inverse Time | Disables the inverse time trip | 0= Trip Enabled | 1 |
|
|
| 1= Trip Disabled |
|
| Display | Disables the display (keypad) trip | 0= Trip Enabled | 0 |
| (Keypad) |
| 1= Trip Disabled |
|
| Jog Accel Time | As P4, for Jog | 0.0 to 3000.0s | 1.0 |
| Jog Decel Time | As P5, for Jog | 0.0 to 3000.0s | 1.0 |
| Ramp Type | Selects the ramp type | 0=LINEAR | 0 |
|
|
| 1=S |
|
| S Ramp Jerk | Rate of change of acceleration of the curve in | 0.01 to 100.00s3 | 10.00s3 |
|
| units per second3 |
|
|
| S Ramp | When True and the S Ramp is selected, forces | 0=FALSE | 1 |
| Continuous | a smooth transition if the speed setpoint is | 1=TRUE |
|
|
| changed when ramping. The curve is controlled |
|
|
|
| by the S Ramp Jerk parameter. |
|
|
|
| When False, there is an immediate transition |
|
|
|
| from the old curve to the new curve |
|
|
| Skip | The center frequency of skip band 1 in Hz | 0.0 to 240.0 Hz | 0.0 |
| Frequency 1 |
|
|
|
| Skip Frequency | The width of skip band 1 in Hz | 0.0 to 60.0 Hz | 0.0 |
| Band 1 |
|
|
|
| Skip | The center frequency of skip band 2 in Hz | 0.0 to 240.0 Hz | 0.0 |
| Frequency 2 |
|
|
|
| Skip Frequency | The width of skip band 2 in Hz | 0.0 to 60.0 Hz | 0.0 |
| Band 2 |
|
|
|
| Auto Restart | Determines the number of restarts that will be | 0 to 10 | 0 |
| Attempts | permitted before requiring an external fault |
|
|
|
| reset |
|
|
| Auto Restart | The delay between restart attempts for a trip | 0.0 to 600.0 s | 10.0s |
| Delay | included in Auto Restart Triggers and Auto |
|
|
|
| Restart Triggers+. The delay is measured from |
|
|
|
| all error conditions clearing |
|
|
| Auto Restart | Allows Auto Restart to be enabled for a | 0x0000 to 0xFFFF | 0x0000 |
| Triggers | selection of trip conditions. Refer to Section 5 |
|
|
MN735 |