Display | Trip Message and Meaning | Possible Reason for Trip |
|
| Motor loading too great |
|
| FIXED BOOST level set too high |
| DC LINK RIPPLE | Supply imbalance in a |
| A dc link ripple alert | Poor supply regulation in a |
| CURRENT LIMIT | See OVERCURRENT above |
| Software overcurrent trip |
|
| TERMINAL 3 OVERLOAD | AIN2 overload – overcurrent applied in Current |
|
| mode |
| TERMINAL 4 OVERLOAD | +10V REF overload warning – 10mA maximum |
| TERMINAL 5 OVERLOAD | AOUT overload – 10mA maximum |
| TERMINAL 9 OVERLOAD | DIN3 overload – 20mA maximum |
| TERMINAL 10 OVERLOAD | DOUT2 overload – 20mA maximum |
| Product Code Error | Switch unit off/on. If persistent, return unit to |
|
| factory |
| Calibration Data Error | Switch unit off/on. If persistent, return unit to |
|
| factory |
| Configuration Data Error |
|
General Failures
Problem | Possible Cause | Remedy |
Inverter will not | Fuse blown | Check supply details, fit correct fuse. |
|
| Check Product Code against Model |
|
| No. |
| Faulty cabling | Check all connections are |
|
| correct/secure. |
|
| Check cable continuity |
|
|
|
Inverter fuse keeps blowing | Faulty cabling or | Check for problem and rectify before |
| connections wrong | replacing with correct fuse |
| Faulty Inverter | Contact Eurotherm Drives |
|
|
|
Cannot obtain | Incorrect or no supply | Check supply details |
state | available |
|
|
|
|
Motor will not run at | Motor jammed | Stop the Inverter and clear the jam |
|
| |
|
|
|
Motor runs and stops | Motor becomes jammed | Stop the Inverter and clear the jam |
|
|
|
| Open circuit speed reference | Check terminal |
| potentiometer |
|
|
|
|
MN735 |