Power Up On initial
.
All parameters are at factory settings. Any changes to these conditions are automatically saved. The drive will initialize on subsequent
How to Change a Parameter Value
You can change the values of parameters stored in the and menus. Refer to “Parameter Definitions” for further information.
•View the parameter to be edited and press to display the parameter’s value.
•Select the digit to be changed (pressing the key moves the cursor from right to left).
•Use the keys to adjust the value. Hold the key momentarily to adjust the value marginally, or hold the key to make rapid changes; the rate of change varies with the time held.
•Press to return to the parameter display. The new value is stored.
Special Menu Features
Reset to Factory Settings (2 button Reset)
Turn power on while pressing the Y and B keys. This loads or restores the factory settings and application 1.
HOLD
Then press
Select Local or Remote
Remote Control Mode: Allows control using digital and analog inputs and outputs. Local control keys are inactive when Remote control mode is selected. In remote mode, the control uses a remote setpoint (analog Input 1).
Local Control Mode: Provides local control and monitoring of the drive using the keypad. In local mode, the control uses the local setpoint parameter (value is adjusted using the keypad).
Note: You can only change between Local and Remote control when the Inverter
is “stopped”, and either | or the Local Setpoint is displayed. |
Remote to Local |
|
Note: For safety reasons, the control will not return to Remote mode if this will cause the drive to start. Verify that the RUN and JOG inputs are low.
MN735 |