Table 4-1

Parameter Definitions Continued

 

Display

Parameter

Description

 

 

Range

Factory

 

 

 

 

 

 

 

Setting

 

 

 

SET::IN Menu Continued

 

 

 

DIN 1 VALUE

The input signal after inversion (if any).

0= False

0

 

~

 

 

 

 

1= True

 

 

DIN 2 VALUE

The input signal after inversion (if any).

0= False

0

 

~

 

 

 

 

1= True

 

 

DIN 3 VALUE

The input signal after inversion (if any).

0= False

0

 

~

 

 

 

 

1= True

 

 

DIN 4 VALUE

The input signal after inversion (if any).

0= False

0

 

~

 

 

 

 

1= True

 

 

AIN 1 VALUE

The analog input signal with scaling and offset.

x.x%

x.x%

 

~

 

 

 

 

 

 

 

AIN 2 VALUE

The analog input signal with scaling and offset.

x.x%

x.x%

 

~

 

 

 

 

 

 

 

 

 

SET::OUT Menu

 

 

 

 

AOUT 1

ANALOG OUTPUT

 

0= NONE

1

 

SOURCE

 

1= DEMAND

 

 

 

0 NONE

Scale

 

2= CURRENT

 

 

 

1 DEMAND %

 

3= PI ERROR

 

 

 

Offset

 

 

 

 

2 CURRENT %

0–10V

 

 

 

3 PI ERROR %

Absolute

 

4= RAISE/LOWER

 

 

 

4 RAISE/LOWER

 

OUTPUT

 

 

 

 

 

 

 

 

OUTPUT%

 

 

 

 

 

AOUT 1 SCALE

 

SCALE

OFFSET

ABS

-300.0 to 300.0

100.0%

 

 

 

 

 

 

 

Value

X

+

X Output

 

 

 

AOUT 1

 

 

 

 

-300.0 to 300.0%

0.00%

 

OFFSET

 

 

 

 

 

 

 

AOUT 1

 

 

 

 

0= False

0

 

ABSOLUTE

 

 

 

 

1= True

 

 

AOUT 1 VALUE

 

 

 

 

-300.0 to 300.0%

0.0%

 

~

 

 

 

 

 

 

 

DOUT 2

DIN4 / DOUT2

 

 

0= NONE (DIN4)

0

 

SOURCE

0 NONE

 

 

1= HEALTH

 

 

 

1 HEALTH

 

 

2= TRIPPED

 

 

 

2 TRIPPED

Invert

 

3= RUNNING

 

 

 

3 RUNNING

 

 

 

 

Output

 

4= AT ZERO

 

 

 

4 AT ZERO

 

 

 

 

 

 

5= AT SPEED

 

 

 

5 AT SPEED

 

 

 

 

 

6 AT LOAD

 

 

6= AT LOAD

 

 

DOUT 2

(OUTPUT) As SIP01. Set to 0 for applications

As SIP01

0

 

INVERT

1 & 5.

 

 

 

 

 

 

DOUT 2

The output signal that represents the OP21

0= False

0

 

VALUE ~

choice.

 

 

 

1= True

 

RELAY

RELAY

SOURCE

0 NONE

 

1

HEALTH

 

2

TRIPPED

 

3

RUNNING

 

4

AT ZERO

 

5

AT SPEED

 

6

AT LOAD

Invert Output

0= NONE

2

1= HEALTH 2= TRIPPED 3= RUNNING 4= AT ZERO 5= AT SPEED 6= AT LOAD