Table 4-1 Parameter Definitions Continued

Display

Parameter

Description

 

 

 

 

Range

Factory

 

 

 

 

 

 

 

 

Setting

Parameters P501 and P502 are visible in the PAR menu when Application 5 is selected in parameter P1

 

 

PI P GAIN

The PID •P"roportional gain

 

 

0.00 to 100.00

1.00

 

PI I GAIN

The PID •I"ntegral gain

 

 

0.00 to 100.00

0.00

 

PID D GAIN ~

The PID •D"erivative gain

 

 

0.00 to 100.00

0.00

 

PID D FILTER

A first order lag filter to help attenuate high

 

0.05 to 10.00s

0.05s

 

TC ~

frequency noise on the derivative term. This

 

 

 

 

parameter determines the filter time constant.

 

 

 

PID FEEDBACK

A multiplier applied to the PID feedback signal

-10.00 to 10.00

1.00

 

GAIN ~

 

 

 

 

 

 

 

 

PID LIMIT ~

Determines the maximum positive and negative

0.00 to 300.00%

0.00

 

 

excursion (Limit) of the PID output

 

 

 

 

PID SCALING

An overall scale factor which is applied after the

-3.0000 to 3.0000

0.00

 

~

PID positive and negative limit clamps

 

 

 

 

PID ERROR

Error=(Setpoint-Feedback) x (Feedback Gain)

x.xx %

x.xx %

 

~

 

 

 

 

 

 

 

 

PID OUTPUT

The output of the PID function block

 

x.xx %

x.xx %

 

~

 

 

 

 

 

 

 

 

 

 

SET::IN Menu

 

 

 

 

 

DIN 1 INVERT

True =Inverts the input signal.

 

 

0= False

0

 

 

 

 

 

 

 

1= True

 

 

DIN 2 INVERT

True =Inverts the input signal.

 

 

0= False

0

 

 

 

 

 

 

 

1= True

 

 

DIN 3 INVERT

True =Inverts the input signal.

 

 

0= False

0

 

 

 

 

 

 

 

1= True

 

 

DIN 4 INVERT

True =Inverts the input signal.

 

 

0= False

0

 

 

 

 

 

 

 

1= True

 

 

AIN 1 SCALE

TYPE

SCALE

OFFSET

 

-150.0 to 150.0%

100.0%

 

 

 

 

 

 

 

UNPROCESSED

X

+

VALUE

 

 

 

 

INPUT

 

 

 

 

 

0 to 100% of selected TYPE

 

 

 

 

 

AIN 1 OFFSET

 

 

 

 

 

-100.0 to 100.0%

0.00%

 

AIN 1 TYPE

 

 

 

 

 

0= 0-10V

0

 

 

 

 

 

 

 

1= 0-5V

 

 

AIN 2 SCALE

TYPE

SCALE

OFFSET

 

-150.0 to 150.0%

100.0%

 

 

 

 

 

 

 

UNPROCESSED

X

+

VALUE

 

 

 

 

INPUT

 

 

 

 

 

0 to 100% of selected TYPE

 

 

 

 

 

AIN 2 OFFSET

 

 

 

 

 

-100.0 to 100.0%

0.0%

 

AIN 2 TYPE

 

 

 

 

 

0= 0-10V

3

 

 

 

 

 

 

 

1= 0-5V

 

 

 

 

 

 

 

 

2= 0-20mA

 

 

 

 

 

 

 

 

3= 4-20mA

 

4–8 Start–Up and Operation

MN735

Page 37
Image 37