annunciation information, and switch between heating loops (Central Heat and Domestic Hot Water), as shown in Figure 25. If a password is required to change any of the settings on this page, the user can press the Login button to enter the password.

2.2.12ANNUNCIATION PAGE

►OPERATION►

ANNUNCIATION

Figure 26 Annunciation Page

The annunciation page shows the status of the load control input (call for heat), pre-ignition interlock (proof of gas valve closure), and the running interlock strings. The components are listed in the order they are wired. This page can be called up at any time from the operation page (Figure 25). This page is very helpful for troubleshooting a lockout 67 (ILK off). All components for a given string are wired in series. The first component that indicates off will be the safety device to check.

Date: 8-4-2010

Revision: 0

Form: 2396

2.2.13MODULATION CONFIGURATION

► CONFIGURE ► MODULATION

CONFIGURATION

Figure 27 Modulation Configuration

The modulation configuration page is used to set the modulation range of the boiler. The recommended maximum and minimum rpm values can be found in

2.2.14FIRING RATE CONTROL PAGE

► OPERATION ► FIRING RATE

FIELD

Figure 28 Firing Rate Control Page

The firing rate control page enables the user to change how the firing rate is controlled. The first option is for automatic control based on the current set point. The second option enables