algorithm. (Any Solas set to Use First will precede any that are set to Equalize Run time.) If set to Use Last, then this burner will be used only after all Use First and Equalize Runtime Solas have been brought online.

SLAVE SEQUENCE ORDER: 0-255

Slave sequence order is used to determine the order in which Solas will be used (staged on) for those Solas which the same Slave mode setting. Numbers may be skipped, that is 3 will be first if there is no 1 or 2. Note: For Equalize Runtime purposes, 1 does not mean the Sola will be used first every time; that will vary over time based on the master's run time equalization scheme. In this case the sequence number determines the relative order in which Sola controls will be used in a round-robin scheme. If the slave sequence number value is zero, then the slave Sola's ModBus address will be used instead. If two Solas which are set the same mode both have the same sequence number then an alert will occur and the order in which they are used will be arbitrary and is not guaranteed to be repeatable.

DEMAND-TO-FIRING DELAY: MM:SS OR NONE

This delay time is needed by the LL master to determine the length of time to wait between requesting a slave Sola to fire and detecting that it has failed to start. It should be set to the total time normally needed for the burner to transition from Standby to Run, including such things as transition to purge rate, prepurge time, transition to lightoff rate, all ignition timings, and some extra margin.

BASE LOAD RATE: RPM OR %

This specifies the preferred firing rate of a burner, which is used for some types of control algorithms.

FAN DURING OFF-CYCLE RATE: RPM OR % (0=DISABLE)

This determines if or where the fan is to be operating during the standby period.

4.7LL MASTER OPERATION AND SETUP

LLmaster operation is subdivided into the following functions:

Overall control - The LL master has

61

Date: 8-4-2010

Revision: 0

Form: 2396

parameters that enable and disable its operation.

Periodic data polling - The LL master uses polling to discover new slave Sola devices and to periodically refresh the information it has about a known slave Sola devices.

Slave control - the LL master sends each active slave a command and also performs a slave status read for each known slave device. It also sends a Master status broadcast that is heard by all slaves.

Slave status manager - The LL master keeps track of slave status for each Sola that is enabled as a slave device.

Demand and priority - different sources of demand can cause the LL master to operate in different ways. These sources have a priority relationship.

Modulation - each demand source has one or more setpoints that may be active and an operation sensor. These are used to detect turn- on and turn-off conditions. The difference between operating point and setpoint determines the LL master's firing rate.

Stager - the stager determines when slave Solas should turn on as the need for heat increases, and when they should turn off as the need for heat decreases.

Rate allocation - the PID block's output is used to determine the firing rate of each slave Sola using various rate allocation techniques.

Add-stage methods - various methods can be used to determine when a new stage should be added.

Drop-stage methods - various methods can be used to determine when a stage should be dropped

Sequencer - the Sola sequencer determines which Sola will be the next one to turn on or turn off.

4.7.1OVERALL CONTROL

LLMASTER ENABLE: DISABLE, ENABLE, LL MASTER MODBUS PORT: MB1, MB2 If Disable is selected then all LL master functions are inactive. If Enable is selected then it acts as the active bus master on the ModBus port it is assigned. LL OPERATION SWITCH: OFF, ON This controls the LL master in the same way that the Burner switch controls a stand-alone Sola. If "On" then the LL master is enabled to operate. If this parameter is "Off" then the LL master turns

Page 67
Image 67
Bryan Boilers 200, Triple-Flex 150, 250, & 300 service manual LL Master Operation and Setup, Overall Control