2.2.21CENTRAL HEAT

CONFIGURATION

► CONFIGURE

CH - CENTRAL HEAT CONFIGURATION

 

Date:

8-4-2010

 

Revision:

0

 

Form:

2396

 

 

 

Setpoint source

Local

 

 

S2 (J8-6) 4-20mA

Setpoint

Setpoint for normal

 

Central Heat modulation:

 

50 °F to 190 °F

Time of day setpoint

Setpoint when Time Of

 

Day switch is on. 50 °F to

 

190 °F

 

Off hysteresis

Differential above

 

setpoint when boiler is

 

turned off. 2 °F to 5 °F

On hysteresis

Differential

from setpoint

 

when boiler is turned on.

 

2 °F to 30 °F

4 mA water temperature

50 °F to 190 °F

20 mA water temperature

50 °F to 190 °F

Figure 36 Central Heat Configuration (Central Heat Page)

CH enable

Disable or Enable Central

 

Heating Loop

Demand switch

Sensor for Central Heat

 

demand:

 

Sensor only

 

Sensor & STAT terminal

 

Sensor & Remote Stat

 

LCI & Sensor

Outdoor reset

Enabled

 

Disabled

CH has priority over Lead

Yes, No, Cancel

Lag

 

Figure 38 Central Heat Configuration (Modulation Page)

Modulation sensor

Outlet

sensor,

Inlet

 

 

sensor, S5 (J8-11)

 

Modulation Rate Source

Local

 

 

P-gain Gain

 

applied for the P portion

 

 

of the PID equation 0-400

I-gain Gain

 

applied for the I portion of

 

 

the PID equation 0-400

D-gain

 

Gain applied for the D

 

 

portion

of the

PID

 

 

equation 0-400

 

Hysteresis

step time

Time between hysteresis

(0=Disable

hysteresis

step changes: 0-600

stepping)

 

seconds

 

 

2.2.22SOUND PRESSURE LEVELS

Figure 37 Central Heat Configuration (Setpoint Page)

Sound pressure levels were measured at 4-1/2’ above the floor and 3’ from the boiler at the front, rear and two sides. See Table 6 for decibel readings.

 

 

Decibel Readings

 

Model

Front

Rear

Tube

Right

Side

Side

 

 

 

27

Page 33
Image 33
Bryan Boilers 250, Triple-Flex 150, & 300, 200 service manual Sound Pressure Levels, Pid