Code | Description |
| Recommended Troubleshooting of Lockout Codes |
|
| Code | |||
122 | Lightoff | rate | 1. | Check wiring and correct any potential wiring errors. |
|
| L | ||
| proving failed | 2. | Check VFDs ability to change speeds. |
|
|
| |||
123 | Purge |
| rate | proving | 3. | Change the VFD |
|
| L |
| failed |
|
|
| 4. | If the fault persists, replace the module. |
|
|
|
|
|
|
|
|
|
|
|
|
|
124 | High |
| fire | switch | 1. | Check wiring and correct any potential wiring errors. |
|
| H |
| OFF |
|
|
| 2. Check High Fire Switch to assure proper function (not welded |
| |||
125 | High |
| fire | switch | or jumpered). |
|
| H | |
| stuck ON |
| 3. Manually drive the motor to the High Fire position and adjust |
|
| ||||
126 | Low |
| fire | switch | the HF switch while in this position and verify voltage through |
| H | ||
| OFF |
|
|
| the switch to the HFS input with a voltmeter. |
|
|
| |
127 | Low |
| fire | switch | 4. | If steps |
| H or L | |
| stuck ON |
| module. |
|
|
| |||
128 | Fan | speed | failed | 1. | Check wiring and correct any potential wiring errors. |
|
| H or L | |
| during prepurge | 2. | Check VFDs ability to change speeds. |
|
|
| |||
129 | Fan | speed | failed | 3. | Change the VFD |
|
| H or L | |
| during preignition | 4. | If the fault persists, replace the module. |
|
|
| |||
130 | Fan | speed | failed |
|
|
|
| H or L | |
| during ignition |
|
|
|
|
| |||
131 | Fan |
| movement |
|
|
|
| H | |
| detected | during |
|
|
|
|
| ||
| standby |
|
|
|
|
|
| ||
132 | Fan | speed | failed |
|
|
|
| H | |
| during run |
|
|
|
|
|
| ||
133- | RESERVED |
|
|
|
|
|
| ||
135 |
|
|
|
|
|
|
|
|
|
136 | Interrupted | Airflow | 1. | Check wiring and correct any possible wiring errors. |
|
| H | ||
| Switch | failed to | 2. | Check Interrupted Airflow switch(es) to assure proper |
|
| |||
| close |
|
|
| function. |
|
|
| |
|
|
|
|
| 3. | Verify voltage through the airflow switch to the IAS input with |
|
| |
|
|
|
|
| a voltmeter. |
|
|
| |
|
|
|
|
| 4. | If steps |
|
| |
|
|
|
|
| module. |
|
|
| |
137 | ILK failed to close | 1. | Check wiring and correct any possible shorts. |
|
| H | |||
|
|
|
|
| 2. | Check Interlock (ILK) switches to assure proper function. |
|
|
|
|
|
|
|
| 3. Verify voltage through the interlock string to the interlock input |
| |||
|
|
|
|
| with a voltmeter. |
|
|
| |
|
|
|
|
| 4. | If steps |
|
| |
|
|
|
|
| module. |
|
|
| |
138- | RESERVED |
|
|
|
|
|
| ||
148 |
|
|
|
|
|
|
|
|
|
| FAULT | CODES |
|
|
|
|
| ||
| 149 |
| THROUGH |
|
|
|
|
| |
| 165 | ARE | OEM |
|
|
|
|
| |
| SPECIFIC | FAULT |
|
|
|
|
| ||
| CODES. |
|
|
|
|
|
| ||
149 | Flame detected | OEM Specific |
|
| H or L | ||||
|
|
|
|
| 1. | Holds if flame detected during Safe Start check up to Flame |
|
| |
|
|
|
|
| Establishing period. |
|
|
| |
150 | Flame not detected | OEM Specific |
|
| H | ||||
|
|
|
|
| 1. | Sequence returns to standby and restarts sequence at the |
|
| |
|
|
|
|
| beginning of Purge after the HF switch opens. if flame detected |
|
| ||
|
|
|
|
| during Safe Start check up to Flame Establishing period. |
|
|
| |
151 | High fire switch ON | OEM Specific |
|
| H or L | ||||
|
|
|
|
|