(Figure 34). The normal reset curve is shown in green and the time of day is red.

Figure 34 Outdoor Reset Curve

► CONFIGURE

SENSOR CONFIGURATION

(Sensor) S5 (J8-11) sensor

(Connector type) 10K NTC single non-safety

(Outdoor temperature source) S5 (J8-11) sensor

Figure 35 Outdoor Reset Sensor Configuration

Note:

Update the sensor name to ‘Outdoor Sensor’ by selecting a different sensor then reselecting the S5 (J8-11) sensor.

26

Date: 8-4-2010

Revision: 0

Form: 2396

► CONFIGURE

CH - CENTRAL HEAT CONFIGURATION

(page) CENTRAL HEAT

(Outdoor Reset) ENABLED

Note:

y1 is the maximum water setpoint value found in ‘CH – Central heat Configuration’ on the ‘Setpoint’ page.

2.2.20REMOTE SETPOINT (4 – 20

MA)

► CONFIGURE

SENSOR CONFIGURATION

(Sensor) S2 (J8-6) sensor

(Connector type) 4-20mA

SAFETY VERIFICATION 2.2.9

► CONFIGURE

CH - CENTRAL HEAT CONFIGURATION

(page) SETPOINT

(Setpoint Source) S2 (J8-6) 4-20mA

(4 mA water temperature) MIN

(20 mA water temperature) MAX

Page 32
Image 32
Bryan Boilers Triple-Flex 150, 250, & 300, 200 Configure Sensor Configuration, Configure CH Central Heat Configuration