Date:

8-4-2010

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Revision:

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Form:

2396

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Code

Description

 

 

 

 

Recommended Troubleshooting of Lockout Codes

 

 

Code

32-46

Internal

 

 

 

fault:

 

 

 

 

 

 

 

 

 

L

 

 

 

Safety

Key

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

through 14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

47

 

Flame

Rod

to

 

 

 

 

 

 

 

 

 

H

 

 

 

ground leakage

 

 

 

 

 

 

 

 

 

 

 

 

 

48

 

Static

flame

(not

 

 

 

 

 

 

 

 

 

H

 

 

 

flickering)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

49

 

24VAC voltage low/

1.

Check the Module and display connections.

 

 

H

 

 

 

high

 

 

 

 

 

 

 

2.

Check the Module power supply and make sure that both

 

 

 

 

 

 

 

 

 

 

 

 

 

frequency, voltage and VA meet the specifications.

 

 

 

 

50

 

Modulation fault

 

 

Internal sub-system fault.

 

 

H

51

 

Pump fault

 

 

 

1.

Review alert messages for possible trends.

 

 

H

52

 

Motor

tachometer

2.

Correct possible problems.

 

 

H

 

 

 

fault

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

53

 

AC

inputs

phase

1.

Check the Module and display connections.

 

 

L

 

 

 

reversed

 

 

 

2.

Check the Module power supply and make sure that both

 

 

 

 

 

 

 

 

 

 

 

 

 

frequency and voltagemeet the specifications.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.

On 24Vac applications, assure that J4 terminal 10 and J8

 

 

 

 

 

 

 

 

 

 

 

 

 

terminal 2 are connected together.

 

 

 

 

54-57

RESERVED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

58

 

Internal

fault: HFS

Internal Fault.

 

 

L

 

 

 

shorted to IAS

 

 

1.

Reset Module.

 

 

 

 

59

 

Internal

Fault: Mux

2.

If fault repeats, replace module

 

 

L

 

 

 

pin shorted

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

 

Internal Fault: HFS

 

 

 

 

 

 

 

 

 

L

 

 

 

shorted to LFS

 

 

 

 

 

 

 

 

 

 

 

 

 

61

 

Anti short cycle

 

 

Will not be a lockout fault. Hold Only.

 

 

H

62

 

Fan

speed

not

 

 

 

 

 

 

 

 

 

H

 

 

 

proved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

63

 

LCI OFF

 

 

 

1.

Check wiring and correct any faults.

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

2.

Check Interlocks connected to the LCI to assure proper

 

 

 

 

 

 

 

 

 

 

 

 

 

function.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.

Reset and sequence the module; monitor the LCI status.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.

If code persists, replace the module

 

 

 

 

64

 

PII OFF

 

 

 

 

 

 

1.

Check wiring and correct any faults.

 

 

L

 

 

 

 

 

 

 

 

 

 

 

 

2.

Check Preignition Interlock switches to assure proper

 

 

 

 

 

 

 

 

 

 

 

 

 

functioning.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.

Check the valve operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.

Reset and sequence the module; monitor the PII status.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.

If code persists, replace the module.

 

 

 

 

 

65

 

 

Interrupted

Airflow

 

 

1.

Check wiring and correct any possible shorts.

 

 

 

 

H or L

 

 

 

 

 

Switch OFF

 

 

 

 

 

2.

Check airflow switches to assure proper functioning.

 

 

 

 

 

 

66

 

 

Interrupted

 

Airflow

 

 

3.

Check the fan/blower operation.

 

 

 

 

 

H or L

 

 

 

 

 

Switch ON

 

 

 

 

 

4.

Reset and sequence the module;

monitor the airflow status.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.

If code persists, replace the module.

 

 

 

 

 

67

 

ILK OFF

 

 

 

 

1.

Check wiring and correct any possible

shorts.

 

 

L

 

 

 

 

 

 

 

 

 

 

 

 

2.

Check Interlock (ILK) switches to assure proper function.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3. Verify voltage through the interlock string to the interlock input

 

 

 

 

 

 

 

 

 

 

 

 

 

with a voltmeter.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.

If steps 1-3 are correct and the fault persists, replace the

 

 

 

 

 

 

 

 

 

 

 

 

 

module.

 

 

 

 

41

Page 47
Image 47
Bryan Boilers 200, Triple-Flex 150, 250, & 300 service manual Lci Off, Pii Off, Ilk Off