Recommended Troubleshooting of Lockout Codes

 

 

Code

 

 

 

 

1.

Check wiring and correct any potential wiring errors.

 

 

 

 

 

 

 

2. Check High Fire Switch to assure proper function (not welded

 

 

 

 

 

or jumpered).

 

 

 

 

 

 

 

3.Manually drive the motor to the High Fire position and adjust

 

 

 

 

 

 

the HF switch while in this position and verify voltage through

 

 

 

 

 

 

the switch to the HFS input with a voltmeter.

 

 

 

 

 

 

 

4.

If steps 1-3 are correct and the fault persists, replace the

 

 

 

 

 

 

module.

 

 

 

152

Combustion

 

OEM Specific

 

 

H or L

 

pressure ON

 

1.

Check wiring and correct any errors.

 

 

 

153

Combustion

 

2.

Inspect the Combustion Pressure Switch to make sure it is

 

H or L

 

Pressure Off

 

working correctly.

 

 

 

 

 

 

 

3.

Reset and sequence the relay module.

 

 

 

 

 

 

 

4.

During STANDBY and PREPURGE, measure the voltage

 

 

 

 

 

 

between J6 terminal 5 and L2 (N). Supply voltage should be

 

 

 

 

 

 

present. If not, the lockout switch is defective and needs

 

 

 

 

 

 

replacing.

 

 

 

 

 

 

 

5.

If the fault persists, replace the relay module.

 

 

 

154

Purge

Fan

switch

OEM Specific

 

 

H or L

 

On

 

 

1.

Purge fan switch is on when it should be off.

 

 

 

155

Purge

fan

switch

2.

Check wiring and correct any errors.

 

 

H or L

 

OFF

 

 

3.

Inspect the Purge Fan switch J6 terminal 3 and its

 

 

 

 

 

 

connections. Make sure the switch is working correctly and is

 

 

 

 

 

 

not jumpered or welded.

 

 

 

 

 

 

 

4.

Reset and sequence the relay module.

 

 

 

 

 

 

 

5.

If the fault persists, replace the relay module.

 

 

 

156

Combustion

 

OEM Specific

 

 

H or L

 

pressure

and

1.

Check that flame is not present in the combustion chamber.

 

 

Flame ON

 

Correct any errors.

 

 

 

157

Combustion

 

2.

Make sure that the flame detector is wired to the correct

 

L

 

pressure

and

terminal.

 

 

 

 

Flame OFF

 

3.

Make sure the F & G wires are protected from stray noise

 

 

 

 

 

 

pickup.

 

 

 

 

 

 

 

4.

Reset and sequence the module, if code reappears, replace

 

 

 

 

 

 

the flame detector.

 

 

 

 

 

 

 

5.

Reset and sequence the module, if code reappears, replace

 

 

 

 

 

 

the module.

 

 

 

158

Main valve ON

OEM Specific

 

 

L

159

Main valve OFF

1.

Check Main Valve terminal wiring and correct any errors.

 

 

L

 

 

 

 

2.

Reset and sequence the module. If fault persist, replace the

 

 

 

 

 

 

module.

 

 

 

160

Ignition ON

 

OEM Specific

 

 

L

161

Ignition OFF

 

1.

Check Ignition terminal wiring and correct any errors.

 

 

L

 

 

 

 

2.

Reset and sequence the module. If fault persist, replace the

 

 

 

 

 

 

module.

 

 

 

162

Pilot valve ON

OEM Specific

 

 

L

163

Pilot valve OFF

1.

Check Pilot Valve terminal wiring and correct any errors.

 

 

L

 

 

 

 

2.

Reset and sequence the module. If fault persist, replace the

 

 

 

 

 

 

module.

 

 

 

164

Block intake ON

OEM Specific

 

 

L