Recommended Troubleshooting of Lockout Codes

 

Code

 

 

 

 

2.

Replace the stack sensor.

 

 

 

 

 

 

3.

If previous steps are correct and fault persists, replace the

 

 

 

 

 

module

 

 

96

Outdoor

sensor

1.

Check wiring and correct any possible errors.

 

H

 

fault

 

 

2.

Replace the outdoor sensor.

 

 

 

 

 

 

3.

If previous steps are correct and fault persists, replace the

 

 

 

 

 

module.

 

 

97

Internal Fault: A2D

Internal Fault.

 

L

 

mismatch.

 

1.

Reset Module.

 

 

98

Internal

Fault:

2.

If fault repeats, replace module.

 

L

 

Exceeded

VSNSR

 

 

 

 

 

voltage tolerance

 

 

 

 

99

Internal

Fault:

 

 

 

L

 

Exceeded

28V

 

 

 

 

 

voltage tolerance

 

 

 

 

100

Pressure

Sensor

1.

Verify the Pressure Sensor is a 4-20ma source.

 

H

 

Fault

 

 

2.

Check wiring and correct any possible errors.

 

 

 

 

 

 

3.

Test Pressure Sensor for correct operation.

 

 

 

 

 

 

4.

Replace the Pressure sensor.

 

 

 

 

 

 

5.

If previous steps are correct and fault persists, replace the

 

 

 

 

 

module.

 

 

 

 

 

 

 

 

101-

RESERVED

 

 

 

 

104

 

 

 

 

 

 

 

105

Flame detected out

1.

Check that flame is not present in the combustion chamber.

H or L

 

of sequence

Correct any errors.

 

 

 

 

 

 

2.

Make sure that the flame detector is wired to the correct

 

 

 

 

 

terminal.

 

 

 

 

 

 

3.

Make sure the F & G wires are protected from stray noise

 

 

 

 

 

pickup.

 

 

 

 

 

 

4.

Reset and sequence the module, if code reappears, replace

 

 

 

 

 

the flame detector.

 

 

 

 

 

 

5.

Reset and sequence the module, if code reappears, replace

 

 

 

 

 

the module.

 

 

106

Flame lost in MFEP

1. Check pilot valve (Main Valve for DSI) wiring and operation -

L

107

Flame

lost

early in

correct any errors.

 

L

 

run

 

 

2.

Check the fuel supply.

 

 

108

Flame lost in run

3.

Check fuel pressure and repeat turndown tests.

 

L

109

Ignition failed

4.

Check ignition transformer electrode, flame detector, flame

L

 

 

 

 

detector setting or flame rod position.

 

 

 

 

 

 

5. If steps 1 through 4 are correct and the fault persists, replace

 

 

 

 

 

the module.

 

 

110

Ignition

failure

Hold time of recycle and hold option. Will not be a lockout fault.

H

 

occurred

 

Hold Only. Internal hardware test. Not a lockout.

 

 

111

Flame

 

current

 

 

 

H

 

lower

than

WEAK

 

 

 

 

 

threshold

 

 

 

 

 

112

Pilot

test

flame

Interrupted Pilot or DSI application and flame lost when system

L

 

timeout

 

in “test” mode.

 

 

 

 

 

 

1.

Reset the module to restart.

 

 

113

Flame

 

circuit

Flame sensed during Initiate or off cycle, hold 240 seconds, if

L

 

timeout

 

present after 240 seconds, lockout.

 

 