Date: 8-4-2010
Revision: 0
Form: 2396
2.4TROUBLESHOOTING
To support the recommended Troubleshooting, the R7910 has an Alert File. Review the Alert history for possible trends that may have been occurring prior to the actual lockout.
Note Column:
H = Hold message
L = Lockout message
H or L = either Hold or Lockout depending on Parameter Configuration
Table 12 R7910A Lockout and Hold Codes
Code | Description |
|
| Recommended Troubleshooting of Lockout Codes | Code | |
1 | Unconfigured |
| 1.New Device, complete device configuration and safety | L | ||
| safety data |
|
| verification. |
| |
|
|
|
|
| 2. If fault repeats, replace module. |
|
2 | Waiting | for | safety | 1. Device in Configuration mode and safety parameters need | L | |
| data verification | verification and a device needs reset to complete verification. |
| |||
|
|
|
|
| 2. Configuration ended without verification, re enter |
|
|
|
|
|
| configuration, verify safety |
|
|
|
|
|
| parameters and reset device to complete verification. |
|
|
|
|
|
| 3. If fault repeats, replace module |
|
3 | Internal |
|
| fault: | Internal fault | H |
| Hardware fault |
| 1. Reset module |
| ||
4 | Internal |
|
| fault: | 2. If fault repeats, replace module. | H |
| Safety | Relay | key |
|
| |
| feedback error |
|
|
| ||
5 | Internal |
|
| fault: |
| H |
| Unstable | power |
|
| ||
| (DCDC) output |
|
|
| ||
6 | Internal |
|
| fault: |
| H |
| Invalid | processor |
|
| ||
| clock |
|
|
|
|
|
7 | Internal |
|
| fault: |
| H |
| Safety | relay |
| drive |
|
|
| error |
|
|
|
|
|
8 | Internal | fault: Zero |
| H | ||
| crossing |
| not |
|
| |
| detected |
|
|
|
| |
9 | Internal |
|
| fault: |
| H |
| Flame | bias | out of |
|
| |
| range |
|
|
|
|
|
10 | Internal |
|
| fault: |
| L |
| Invalid | Burner |
|
| ||
| control state |
|
|
|
| |
11 | Internal |
|
| fault: |
| L |
| Invalid | Burner |
|
| ||
| control state flag |
|
| |||
12 | Internal |
|
| fault: |
| H |
| Safety | relay |
| drive |
|
|
| cap short |
|
|
|
| |
13 | Internal | fault: | PII |
| H OR L | |
| shorted to ILK |
|
|
| ||
14 | Internal | fault: HFS |
| H OR L | ||
| shorted to LCI |
|
|
| ||
|
|
|
|
| 39 |
|