Grounding the Cisco Nexus 5500 Series Chassis

Chapter 2 Installing the Cisco Nexus 5000 Series Switches

Grounding the Switch

Se n d d o c u m e n t a t i o n c o m m e n t s t o n ex u s 5 k d o c s @ c i s c o . c o m .

Crimping tool to crimp the grounding wire to the grounding lug.

Wire-stripping tool to remove the insulation from the grounding wire.

Grounding the Cisco Nexus 5500 Series Chassis

Note

Warning

Caution

Caution

Warning

Caution

Step 1

Step 2

The chassis has a grounding pad with two threaded M4 holes for attaching a grounding lug. The location of the system ground on the Cisco Nexus 5500 Platform switches is identical to that on the Cisco Nexus 5000 Platform switches.

For the procedure on how to ground the Cisco Nexus 5000 Series switch chassis, see the “Grounding the Cisco Nexus 5500 Series Chassis” section on page 2-22.

When installing or replacing the unit, the ground connection must always be made first and disconnected last. Statement 1046

We recommend grounding the chassis, even if the rack is already grounded.

All power supplies must be grounded. The receptacles of the AC power cables used to provide power to the chassis must be the grounding type, and the grounding conductors should connect to protective earth ground at the service equipment.

When installing or replacing the unit, the ground connection must always be made first and disconnected last.

Statement 1046

Grounding the chassis is required if you are using DC power supplies, even if the rack is already grounded. A grounding pad with two threaded M4 holes is provided on the chassis for attaching a grounding lug. The ground lug must be NRTL listed. In addition, the copper conductor (wires) must be used and the copper conductor must comply with NEC code for ampacity.

To attach the grounding lug and cable to the chassis, follow these steps:

Use a wire-stripping tool to remove approximately 0.75 inches (19 mm) of the covering from the end of the grounding cable.

Insert the stripped end of the grounding cable into the open end of the grounding lug.

 

Cisco Nexus 5500 Platform and Cisco Nexus 5000 Platform Hardware Installation Guide