SpecificationItem
8525BTUs/hrMaxheat dissipation
DCwiring mustmeet your localcodes and regulations,we recommend using alicensed local electrician to
installthe DC wiringneeded.
Todetermine the number of power supply units needed for the blade server, remember that each single slot
serveris budgeted a max 550 W and each full width server is budgeted a max 1100 W. For a more detailed
estimate,contact Cisco Sales.
Supported AC Power Cords and Plugs
TheAC powerconnectors on theblade serverchassis PDU use an IEC 320 C20 socket. Each chassis power
supplyhas a separate power cord. The power cord that you use to connect the blade server power supply units
toan AC power source will have an IEC 320 C19 plug on one end and on the other end one that conforms to
theAC power outlet specifications for your country. See the following table to determine which cord to order
foryour blade server chassispower supply units.When you determinewhich power cord you need to order,
youcan verify that its plugs conform to the power outlets for your facility by clicking on its reference link.
Thejumper power cords, for use in racks, are available as an optional alternative to the standard power cords.
Theoptional jumper power cords have an IEC C19 connector (such as a Cisco RP Series PDU) on the end
thatplugs into the chassisPDUand an IEC C20 connector on the end that plugs into an IEC C19 outlet
receptacle.For more information,contact your CiscoSystems representative.
Onlythe regular power cords or jumperpower cords provided with the chassisare supported.Note

Australia and New Zealand

PowerCord Part NumberCAB-AC-16A-AUS
CordSet Rating16A, 250 VAC
Figure 43: CAB-AC-16A-AUS Power Cord for the Cisco UCS 5108 Blade Server Chassis
Cordsetrating: 16 A, 250 V
Length:14 ft 0 in. (4.26 m)
140586
Connector: IEC 60320 C19
Plug:AU20S3
Cisco UCS 5108 Server Chassis Installation Guide
74 OL-20035-05
Technical Specifications
Supported AC Power Cords and Plugs