Mellanox M4001F/M4001Q Infiniband Switch I/O Module
Externally accessible connectors
Infiniband ports Sixteen QSFP connectors
Mellanox Infiniband Switch Module
Externally accessible connectors
Infiniband ports Eight Infiniband uplink ports
Gb Ethernet Pass-Through Module
Externally accessible connectors
Ethernet Sixteen RJ-45 ports. Pass-through ports support 10/100/1000
Mbps connections.
Fibre Channel Pass-Through Module
Externally accessible connectors
Fibre channel transceiver Sixteen external SFP ports that support 1/2/4 Gbps FC
connections
Environmental
NOTE: For additional information about environmental measurements for specific system configurations, see
dell.com/environmental_datasheets.
Standard Operating Temperature Continuous operation: 10 °C to 35 °C at 10% to 80%
relative humidity (RH), with 26 °C max dew point. De-rate
maximum allowable dry bulb temperature at 1 °C per 300
m above 900 m (1 °F per 550 ft).
Expanded Operating Temperature
NOTE: When operating in the expanded temperature
range, system performance may be impacted.
NOTE: When operating in the expanded temperature
range, ambient temperature warnings may be
reported on the LCD and in the System Event Log.
< 10% of annual operating hours 5 °C to 40 °C at 5% to 85% RH with 26 °C dew point.
NOTE: Outside the standard operating temperature
(10 °C to 35 °C), the system can operate down to 5 °C
or up to 40 °C for a maximum of 10% of its annual
operating hours.
For temperatures between 35 °C and 40 °C, de-rate
maximum allowable dry bulb temperature by 1 °C per 175
m above 950 m (1 °F per 319 ft).
< 1% of annual operating hours –5 °C to 45 °C at 5% to 90% RH with 26 °C dew point.
97