Expanded operating temperature
| For temperatures between 40°C and 45°C, de- |
| rate maximum allowable temperature by 1°C per |
| 125 m above 950 m (1°F per 228 ft). |
Expanded operating temperature restrictions | • Do not perform a cold startup below 5 °C. |
| • 135 W (4 core, 6 core, or 8 core) and 145 W |
| processors are not supported. |
| • The following do not support the expanded |
| operating temperature range: |
| – PCIe SSDs |
| – Non |
| peripheral cards greater than 25 W |
| • When populating the blade slots in the |
| M1000e enclosure with only PowerEdge M630 |
| blades: |
| – Install 86 mm width heat sink for |
| processors of 120 W or more. |
| – Install 68 mm width heat sink for |
| processors of less than 120 W. |
| – If you install a blade with two processors in |
| the M1000e enclosure, all blade slots in the |
| enclosure must have PowerEdge M630 |
| blades with the same configuration |
| (PowerEdge M630 blades with two |
| processors). However, vacant blade slots in |
| the enclosure can be installed with blade |
| blanks. |