Emerson 2700 2 Basic mA wiring, 3 HART/analog single-loopwiring, Output Wiring - Configurable I/O

Models: 2700 1700

1 80
Download 80 pages 1.45 Kb
Page 47
Image 47
Figure 6-2Basic mA wiring

Output Wiring – Model 2700 Configurable I/O Transmitters

Figure 6-2Basic mA wiring

 

 

+

820 Ω maximum loop resistance

 

mA1

 

+

420 Ω maximum loop resistance

 

 

mA2

Output Wiring – Intrinsically Safe

Output Wiring – Configurable I/O

Figure 6-3HART/analog single-loop wiring

+

820 Ω maximum loop resistance

For HART communications:

600 Ω maximum loop resistance

250 Ω minimum loop resistance

HART-

compatible host or controller

Output Wiring – Fieldbus/PROFIBUS

Specifications

Installation Manual

43

Page 47
Image 47
Emerson 2700, 1700 2 Basic mA wiring, 3 HART/analog single-loopwiring, Output Wiring - Intrinsically Safe