Output Wiring – Model 2700 Configurable I/O Transmitters
Figure |
|
| + |
820 Ω maximum loop resistance | – |
| mA1 |
| + |
420 Ω maximum loop resistance | – |
| |
| mA2 |
Output Wiring – Intrinsically Safe
Output Wiring – Configurable I/O
Figure 6-3 HART/analog single-loop wiring
+
–
820 Ω maximum loop resistance
For HART communications:
•600 Ω maximum loop resistance
•250 Ω minimum loop resistance
HART-
compatible host or controller
Output Wiring – Fieldbus/PROFIBUS
Specifications
Installation Manual | 43 |