Specifications

mA Output Load Resistance Value

Rmax = (Vsupply - 12)/0.023*

*If communicating with HART a minimum of 250 Ohms

and 17.75 V supply is needed

 

1000

 

 

 

 

 

 

 

 

 

 

900

 

 

 

 

 

 

 

 

 

(Ohms)

800

 

 

 

 

 

 

 

 

 

700

 

 

 

 

 

 

 

 

 

600

 

 

 

 

 

 

 

 

 

resistor

 

 

 

 

 

 

 

 

 

500

 

 

 

 

 

 

 

 

 

400

 

 

 

 

 

 

 

 

 

External

 

 

 

 

 

 

 

 

 

300

 

 

 

 

 

Operating

 

 

 

 

 

 

 

 

 

 

 

 

200

 

 

 

 

 

Region

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

12

14

16

18

20

22

24

26

28

30

Supply voltage (volts)

One frequency/pulse output (Model 1700 transmitters) or frequency/pulse/discrete output (Model

2700 transmitters):

Intrinsically safe

Externally powered (passive)

Maximum input voltage: 30 VDC, 0.75 watt maximum

Frequency/pulse output (Model 1700/2700):

-Can be used to indicate either flow rate or total; Model 1700 output reports the same flow variable as the mA output, Model 2700 output is independent from mA output

-Scalable to 10,000 Hz

-Linear with flow rate to 12,500 Hz

-Configurable polarity: active high or active low

-Maximum load limit: see following chart

58

Micro Motion® Model 1700 and 2700 Transmitters

Page 62
Image 62
Emerson 1700, 2700 installation manual Operating