Rerange

Reference Manual

00809-0100-4808, Rev CA June 2008

Rosemount 3051N

FIGURE 2-5. Square Root Output Transition Point.

Full Scale Output

 

 

Full Scale

(mA dc)

 

Flow (%)

 

 

 

 

 

Sq. Root

Curve

Transition Point

Linear Section

Sq. Root Curve

Rerange with aManual background Transition

Point

Slope=42

Manual background Slope=1

Rerange

The Range Values command sets the 4 and 20 mA points (lower and upper

 

range values). Setting the range values to the limits of expected readings

 

maximizes transmitter performance. In practice, you may reset the transmitter

 

range values as often as necessary to reflect changing process conditions.

 

You may use one of three methods to rerange the transmitter. Each method is

 

unique; examine all three closely before deciding which method to use.

Rerange with a

Communicator Only

HART Comm.

1, 2, 3, 1, 1

 

 

Reranging using only the communicator changes the values of the analog 4 and 20 mA points independently without a pressure input.

NOTE

Changing the lower or upper range point results in similar changes to the span.

To rerange using only the communicator, enter the fast-key sequence above, select 1 Keypad input, and follow the on-line instructions. Or enter the values directly from the ONLINE screen.