Rosemount 3051N
Reference Manual
Fast Key Sequences
Hot Key options
DIAGNOSTIC
MESSAGES
The Fast Key sequence is a sequence of numerical button presses, corresponding to the menu options that lead you to a given task. Use Table
The Hot Key menu is a
To use a Hot Key option, you must first properly connect the Rosemount 375 Field Communicator to a device. You can access the Hot Key menu from any online window. To use a Hot Key option:
1.Connect the Rosemount 375 Field Communicator to a HART loop or device.
2.Tap the Hot Key. The Hot Key menu is displayed.
3.
The following pages contain a list of messages used by both of the Rosemount 275 and Rosemount 375 HART Communicators (HC) and their corresponding descriptions.
Variable parameters within the text of a message are indicated with <variable parameter>.
Reference to the name of another message is identified by [another message].
Message |
| Description |
|
|
|
1k snsr EEPROM |
| Return to Rosemount Nuclear Instruments, Inc. for repair. |
|
| |
|
|
|
1k snsr EEPROM |
| Use the HART communicator to reset the following parameters: |
| remote seal isolator, remote seal fill fluid, flange material, | |
|
| material, transmitter type, remote seal type, flange type, meter |
|
| type, number of remote seals. |
|
|
|
1k snsr EEPROM |
| Perform a full trim to recalibrate the transmitter. |
|
| |
|
|
|
4k micro EEPROM |
| Return to Rosemount Nuclear Instruments, Inc. for repair. |
|
| |
|
|
|
4k micro EEPROM |
| Use the HART communicator to reset the message field. |
|
| |
|
|
|
4k micro EEPROM |
| Use the HART communicator to reset the following parameters: |
| units, range values, damping, analog output, transfer function, | |
|
| tag, scaled meter values. Perform a d/a trim to ensure that the |
|
| error is corrected. |
|
|
|
4k snsr EEPROM |
| Return to Rosemount Nuclear Instruments, Inc. for repair. |
|
| |
|
|
|
4k snsr EEPROM |
| Use the HART communicator to reset the temperature units |
| and the calibration type. | |
|
|
|