Reference Manual

00809-0100-4808, Rev CA June 2008

Rosemount 3051N

Code

Housing Material

Conduit Entry Size

 

 

 

 

 

 

 

 

 

A

Polyurethane-covered Aluminum

½–14 NPT

 

 

 

 

 

 

J

SST

½–14 NPT

Code

Alternate Flange Options (Requires Materials of Construction Code 0)

 

 

 

 

 

 

 

 

H2

Traditional Flange, 316 SST, SST Drain/Vent, SST Flange Adapter

 

 

 

 

 

 

Code

Mounting Bracket Options

 

 

 

 

 

 

 

 

 

B2

Traditional Flange Bracket for Panel Mounting, CS Bolts

B4

Coplanar Flange Bracket for Panel Mounting, all SST

 

 

 

 

 

 

BS

Universal Traditional Flange Bracket for Panel Mounting (SST), CS Bolts

PM

Traditional Flange Bracket for Pipe Mounting, all SST

 

 

 

 

 

 

Code

Meters (optional)

 

 

 

 

 

 

 

 

 

M5

LCD Meter for Aluminum Housing (Housing Code A only)

M6

LCD Meter for SST Housing (Housing Code J only)

 

 

 

 

 

 

 

Typical Rosemount Number: 3051ND 2 A 2 2 A 1

A B4

 

 

 

 

 

 

 

 

 

(1)All Rosemount 3051N transmitters are provided as standard with transient protection block (TI) and cleaning for < 1 PPM chloride.

(2)Rosemount 3051ND0 is available only with Process Flange Code 0 (Alternate Flange H2), O-ring Code A, and stainless steel process flange bolting.

(3)EPR process o-ring is limited to 2000 psi maximum working pressure and 150 °F (66 °C) process temperature.

CONFIGURATION INFORMATION

NOTE

Mounting Bracket option code must be specified last in the Rosemount model number even if optional meter is ordered.

Transmitter is shipped as follows (unless different calibration is specified).

Engineering Units

Differential/Gage:

in H20 (Range 0, 1, 2, and 3)

 

psi (Range 4 and 5)

Absolute:

psi (all ranges)

 

 

4 mA:

0 (engineering units above)

20 mA:

Upper range limit

 

 

Output:

Linear

Flange type:

Specified Rosemount code option

 

 

Flange material:

Specified Rosemount code option

O-ring material:

Specified Rosemount code option

 

 

Drain/vent:

Specified Rosemount code option

Integral meter:

Installed or none

 

 

Alarm:

Upscale

Software tag:

(blank)

 

 

5-11

Page 61
Image 61
Emerson 3051N Configuration Information, Housing Material Conduit Entry Size, Mounting Bracket Options, Meters optional