Emerson 50 and 60 Hz, 400V, 30-200kVA user manual Auto Restart

Models: 30-200kVA 400V 50 and 60 Hz

1 132
Download 132 pages 10.43 Kb
Page 102
Image 102
7.12Auto Restart

Operating Procedures

7.11Reset After Shutdown for Emergency Stop (EPO Action) or Other Conditions

Once all appropriate measures have been taken to correct the problem indicated by the alarm mes- sage appearing on the operator control panel display, carry out this procedure to restore the UPS to regular operation following an EPO action or for the following reasons: Inverter Overtemperature, Cut-off Overload, Battery Overvoltage, excessive switching (BYP: XFER COUNT BLOCK), etc.

When the user confirms that the fault is cleared & the remote EPO signal is not active:

1.Press the FAULT CLEAR button to let the system exit the Emergency Off state.

2.Press the INVERTER ON button on the right side of the operator control panel for longer than 2 seconds.

NOTE:

UPS manufactured before March 2006 may first require a full power down, i.e., manual opening of the input isolators, for the "Fault Clear" to take effect

NOTE

The rectifier will start again, and the bypass will begin to power the load (for units with internal battery contactor installed, the battery contactor will close). The Rectifier indicator flashes while the rectifier is starting up. When the rectifier enters the normal operation state (about 30 seconds), the rectifier indicator turns green.

NOTE

The rectifier will be turned On automatically when the overtemperature fault disappears at 5 minutes after the disappearance of overtemperature signals.

After the EPO button is pressed, if the input utility is removed, the UPS will shut down completely.

When input utility returns, if the Bypass input power switch (Q2) and UPS output power switch (Q5) are closed, the UPS will startup on Bypass. There will be power at the output terminals of the UPS.

! WARNING

If the internal Manual Bypass Power Switch (Q3) is closed and input utility is present, there will be power at the output terminals of the UPS.

7.12Auto Restart

When the main and bypass sources fail, the UPS draws power from the battery system to supply the load until the batteries are depleted. When the UPS reaches its end of discharge (EOD) threshold, it will shut down.

The UPS will automatically restart and enable output power:

After utility power is restored

If “Auto Recovery after EOD Enabling” is enabled

After the “Auto Recovery after EOD Delay Time” expires (the default delay is 10 minutes) .

If the “Auto Recovery after EOD Enabling” feature is disabled, the user may restart the system man- ually by pressing “Fault Clear” button.

90

Page 102
Image 102
Emerson 50 and 60 Hz, 400V, 30-200kVA user manual Auto Restart