Table 39 Bypass input

Technical Specifications

Table 39 Bypass input

 

Unit of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated Power, kVA

Measurement

30

 

40

 

60

 

80

 

100

120

140

 

160

200

Rated AC Voltage 1

 

 

 

 

 

 

 

 

 

380/400/415 V

 

 

 

 

V (ac)

 

three-phase four-wire, sharing neutral with the rectifier input and

 

 

 

 

 

 

providing neutral reference to the output

 

 

Rated current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380V

A

45

 

61

 

91

 

121

 

151

182

212

 

242

303

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400V

 

43

 

58

 

87

 

116

 

145

174

202

 

230

288

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

415V

 

42

 

56

 

83

 

111

 

139

167

194

 

222

278

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

135% long term

 

125% long term

Overload capacity

%

 

 

 

 

170% 10 min

 

150% 10 min

 

 

 

 

 

 

1000% 100 ms

 

1000% 100 ms

Upstream protection, bypass

 

Thermomagnetic circuit-breaker, rated up to 125% of nominal output

line (by others)

 

 

 

 

 

 

 

current. IEC 60947-2 curve C.

 

 

Current rating of neutral cable

A

 

 

 

 

 

1.7 In

 

 

 

1.52In

1.35In

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency 2

Hz

 

 

 

 

 

 

 

50 / 60

 

 

 

 

Transfer time (between

 

 

 

 

 

 

 

Synchronous transfer: 1ms

 

 

ms

 

Asynchronous transfer (default): 15 ms (50 Hz), 13.3 ms (60 Hz)

Bypass and Inverter)

 

 

 

 

 

 

 

 

or 40, 60, 80, 100 ms selectable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Upper limit: +10, +15 or +20, default +15

 

 

Bypass voltage tolerance

% V (ac)

 

 

 

 

Lower limit –10, -20, -30 or -40, default: -20

 

 

 

 

 

(delay time to accept steady bypass voltage: 10 sec)

 

Bypass frequency tolerance

%

 

 

 

 

 

± 2.5,

±5, ±10 or ±20 default ±10

 

 

 

 

 

 

 

 

 

Synchronisation - Window

Hz

 

 

 

Rated frequency ±2 Hz (selectable ± 0.5 to ± 3Hz)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Factory set to 400V – 380 or 415V selectable by commissioning engineer.

2.Factory set to 50Hz; 60 Hz selectable by commissioning engineer. Bypass condition ignored when UPS set as frequency converter.