Emerson 30-200kVA, 400V Dual Bus System, Cabinet Installation, External Protective Devices

Models: 30-200kVA 400V 50 and 60 Hz

1 132
Download 132 pages 10.43 Kb
Page 62
Image 62
3.4Dual Bus System

UPS Multi-Module Installation

3.4Dual Bus System

3.4.1Cabinet Installation

The Dual Bus System consists of two independent UPS configurations each consisting of one or more UPS modules. Dual Bus Systems are high availability configurations suitable for loads with multiple input terminals. For single input loads an optional Static Transfer Switch may be added and the stan- dard Load Bus Synchroniser activated. Depending on the configuration, follow the appropriate instal- lation instructions for each system.

Place the UPS modules side by side and interconnect as shown below.

The objective of the Dual-bus Synchronizer (DBS) is to keep the output of two independent UPS sys- tems (or parallel systems) in synchronization. One system is designated as the master; the other is designated as the slave. The operating modes covered comprise master and or slave operating inverter or bypass mode.

Figure 33 Typical dual bus system configuration with static transfer switch and Load Bus Synch

Bypass Supply

Bypass Supply

Input

Rectifier

Input

Rectifier

Input

Rectifier

Input

Rectifier

Q1

Q1

Q1

Q1

UPS1

CHARGER

RECTIFER

INVERTER

Q2

UPS1

RECTIFER

CHARGER

INVERTER

Q2

UPS1

CHARGER

RECTIFER

INVERTER

Q2

UPS1

CHARGER

RECTIFER

INVERTER

Q2

Q5

Q3

Q3

LBS

Q3

Q5

Q5

INTERMODULE

 

 

CONTROL CABLE

 

 

INTERMODULE CONTROL CABLE

Q3

Q5

STS

Load

3.4.2External Protective Devices

Refer to the instructions supplied in 1.0 - Single Module UPS Installation.

3.4.3Power Cables

The wiring of power cables is similar to that of single module system. The Bypass and the Main input sources must be referenced to the same neutral potential and input earth leakage monitoring devices, if installed, must be located upstream of the common neutral sinking point. Refer to the instructions in 1.0 - Single Module UPS Installation

50

Page 62
Image 62
Emerson 30-200kVA, 50 and 60 Hz, 400V Dual Bus System, Cabinet Installation, External Protective Devices, Power Cables