Emerson 30-200kVA, 400V Communication and Monitoring, Communication bays and cable location

Models: 30-200kVA 400V 50 and 60 Hz

1 132
Download 132 pages 10.43 Kb
Page 122
Image 122
9.2Communication and Monitoring

Options—For Assembly Inside the UPS Cabinet

9.2Communication and Monitoring

Figure 76 Communication bays and cable location

DB-9

Monitor

Board

(

=

Gland plate for cable exit

Location

Preferred Device This Location

RS-232-1 DB-9 (COM Port 1) - Serial MultiLink Software (Port Setting 2400 Baud)

RS-232-2 DB-9 (COM Port 2 - Service Access Software (Port Setting 9600 Baud)

Location

Preferred Device This Location

Top Bay

Relay Card (no port setting req’d)

Mid Bay

Multiport4 (no port setting req’d)

Bottom Bay

OCWeb LB / OC485 (port setting

 

2400 Baud)

Suggested routing of customer-supplied communication cables

Notes:

a)All Intellislot cards are supported in any bay.

b)Port sharing is:

-PERMITTED between RS232-x DB9 devices and Relay / Multiport4 Intellislot cards (i.e., Serial Multilink software will work from RS232-1 DB9 also when relay card is inserted in the top bay.

-NOT PERMITTED between RS-232-x D-B9 devices and OCWeb / OC485 cards (i.e., Serial MultiLink software will not work from RS232-1 DB-9 when OCWeb card is inserted in the top bay.

c) Monitor board firmware version will be m131 or greater. The version may be verified from the UPS LCD (refer to 8.0 - Operator Control Panel and Display).