Emerson 400V Conformity and Standards, Technical Specifications, Environmental characteristics

Models: 30-200kVA 400V 50 and 60 Hz

1 132
Download 132 pages 10.43 Kb
Page 127
Image 127
10.0TECHNICAL SPECIFICATIONS

Technical Specifications

10.0TECHNICAL SPECIFICATIONS

10.1Conformity and Standards

The UPS has been designed to conform to the following European and international standards:

Table 32 Compliance with European, international standards

Description

Normative reference

 

 

 

 

General and safety requirements for UPS used in operator

EN 50091-1-1 /IEC 62040-1-1 / AS 62040-1-1

access areas

 

 

 

Electromagnetic compatibility (EMC) requirements for UPS

EN 50091-2 / IEC 62040-2

/ AS 62040-2

(Class A)

 

 

 

 

Method of specifying the performance and test requirements of

EN 50091-3 / IEC 62040-3

/ AS 62040-3

(VFI

UPS

SS 111)

 

 

The above mentioned product standards incorporate relevant compliance clauses with generic IEC and EN standards for safety (IEC/EN/AS60950), electromagnetic emission and immunity (IEC/EN/ AS61000 series) and construction (IEC/EN/AS60146 series and 60529). For more details, see below:

Description

Normative reference

Safety for Information technology equipment

EN60950 / IEC 60950 / AS 60950

 

 

Degrees of protection provided by enclosures (IP code).

EN 60529/ IEC60529 / AS 60529

 

 

Semiconductor convertors. Part 1: General requirements and line

IEC 60146-1-1 / AS 60146-1-1

commutated convertors. Part 1-1: Specifications of basic requirements

 

Electromagnetic compatibility (EMC): immunity test

IEC / AS 61000-4-2, -3-4, -5, -6

 

 

Limits for harmonic current emission

IEC / AS 61000-3-2, -3-4, -3-6

 

 

The product standards in Table 32 incorporate relevant compliance clauses with generic IEC and EN standards for safety (IEC/EN/AS60950), electromagnetic emission and immunity (IEC/EN/AS61000 series) and construction (IEC/EN/AS60146 series and 60529).

Table 33 Environmental characteristics

 

Unit of

 

 

 

 

 

 

 

 

 

 

 

 

Rated Power, kVA

Measurement

30

40

60

 

80

 

100

120

 

140

160

200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Acoustic noise level at 1 meter

dBA

55

55

59

 

59

 

62

62

 

65

65

66

 

 

 

 

 

 

 

 

 

 

 

 

Altitude of Operation

m (ft)

 

 

 

 

1000 (3280) above sea level

 

 

derate power by 1% per 100m between 1000 and 2000 (3280-6562)

 

 

Relative Humidity

 

 

 

 

0 to 95% non condensing

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating Temperature

°C (°F)

 

 

 

 

 

0 to 40 (32 to 104)

 

 

 

Note: Battery life is halved for every 10°C increase above 20°C

 

 

UPS Storage-Transport Temperature

°C (°F)

 

 

 

 

 

-20 to 70 (-4 to 158)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Recommended Battery Storage

°C (°F)

 

 

 

 

 

-20 to 30 (-4 to 86)

 

 

 

Temperature

 

 

 

(20 for optimum battery storage)

 

 

 

 

 

 

 

 

115

Page 127
Image 127
Emerson 400V Conformity and Standards, Technical Specifications, Compliance with European, international standards