Emerson 30-200kVA, 400V Multiport-4 Card, SiteNet MultiPort4 Intellislot pin configuration

Models: 30-200kVA 400V 50 and 60 Hz

1 132
Download 132 pages 10.43 Kb
Page 125
Image 125
9.2.3Multiport-4 Card

Options—For Assembly Inside the UPS Cabinet

9.2.3Multiport-4 Card

The Multiport-4 card provides 4 sets of voltage-free contact closures for remote monitoring of alarm conditions UPS operation On Battery and battery low condition. A typical application is to allows a maximum of four computer systems to simultaneously monitor the status (e.g., utility power failure / low battery) of a single UPS.

This card is supported in any of the three NX Intellislot bays.

Figure 79 SiteNet MultiPort4 Intellislot pin configuration

UPS

CPU

CPU

CPU

CPU

Table 30 SiteNet MultiPort4 Intellislot pin assignment

 

Assignment

Pin

Description

 

 

1

Low Battery

 

 

2

Not Used

 

 

3

Not Used

 

 

4

Not Used

 

 

5

Not Used

 

 

6

Not Used

 

 

7

Low Battery Common

 

 

8

Utility Fail Common

 

 

9

Utility Fail

 

 

113