Technical Specifications

Table 34 Efficiency, AC/AC

Input and output voltage 400VAC, battery charged, full rated linear load

 

Unit of

 

 

 

 

 

 

 

 

 

Rated Power, kVA

Measurement

30

40

60

80

100

120

140

160

200

Normal Mode

%

89

90

91

91

90.6

91.1

92.5

92.7

92.8

(dual conversion)

 

 

 

 

 

 

 

 

 

 

ECO Mode

%

94

94.8

94.3

95

95

95.6

95.5

95.7

95.7

Inverter Efficiency (DC/AC) (battery at nominal voltage 480VDC and full-rated linear load)

Battery Mode

%

93

93

94

94

94

94

94

94

94

Heat Losses & Air Exchange—Ventilation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal Mode

kW

 

3.0

 

3.6

 

4.7

 

6.3

 

 

7.9

 

9.5

 

10.8

 

 

11.8

14.5

ECO Mode

kW

 

1.5

 

1.6

 

2.0

 

2.6

 

 

3.5

 

4.3

 

7.0

 

 

7.6

9.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No Load

kW

 

1.3

 

1.4

 

1.9

 

2.4

 

 

3.0

 

3.7

 

4.9

 

 

4.9

5.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Forced air cooling

L/sec

 

333

 

333

 

458

 

458

 

500

 

500

 

671

 

 

671

721

(front intake, top exhaust)

M3/hr

 

1200

 

 

 

 

1650

 

 

 

1800

 

2415

2595

Table 35 Mechanical characteristics

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated Power, kVA

Measurement

30

 

40

 

60

 

 

80

 

 

100

 

120

 

140

 

 

160

 

200

Dimensions, H x W x D

mm (in)

 

1600 x 600 x 825

 

 

 

 

1800 x 700 x 825

1800 x 1000 x 825

 

(63 x 23.6 x 32.5)

 

 

 

(70.8 x 27.5 x 32.5)

(70.8 x 39.4 x 32.5)

 

 

 

 

 

 

Mass, without batteries

kg (lb)

312

 

341

 

401

 

 

445

 

 

720

 

720

 

960

 

 

960

 

1060

(688)

 

(752)

 

(884)

 

(981)

 

(1587)

 

(1587)

 

(2116)

 

 

(2116)

 

(2337)

 

 

 

 

 

 

 

 

 

 

 

Finish

Colour

 

 

 

 

 

 

 

 

 

 

Pantone 877 (Silver grey)

 

 

 

 

 

 

 

 

 

 

eqvl Becker Silver epoxy polyester powder 041-37-2

 

 

 

 

 

 

 

 

 

 

Protection Degree

IEC 60529

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IP20

 

 

 

 

 

 

 

 

 

 

 

 

(finger-proof with front doors open or closed)

 

 

 

 

 

 

 

 

 

 

 

 

Values listed are the mass of the units with options added (ground fault sensor, bypass share inductors and redundant fans).

Table 36 Rectifier AC input (mains)

 

 

Unit of

 

 

 

 

 

 

 

 

 

Rated power, kVA

 

Measurement

30

40

60

80

100

120

140

160

200

Rated AC Input Voltage 1

 

VAC

 

 

 

380/400/415 V

 

 

 

 

 

 

 

(three-phase and sharing neutral with the bypass input)

 

Input voltage tolerance 2

 

VAC

305V to 477V 304V to 208V (output de-rated from 99% to 70%)

Frequency 1

 

Hz

 

 

50/60Hz (tolerance 40Hz to 72Hz)

 

 

Power Factor

 

 

 

 

 

 

 

 

 

 

 

full load

kW/kVA

0.99

0.99

0.99

0.99

0.99

0.99

0.99

0.99

0.99

 

 

 

 

 

 

 

 

 

 

 

half load

0.98

0.98

0.98

0.98

0.98

0.98

0.98

0.98

0.98

 

 

 

 

 

 

 

 

 

 

 

 

 

Input power

 

 

 

 

 

 

 

 

 

 

 

 

rated 3

kVA

27.2

35.9

53.3

71.0

88.8

107

122

139

174

maximum 4

32.9

43.0

64.6

85.2

107

128

159

182

228

 

Input current

 

 

 

 

 

 

 

 

 

 

 

 

rated 3

A

39

52

77

103

128

154

177

201

252

maximum 4

48

62

93

123

154

185

231

264

330

 

Harmonic Current Distort (with

THID

3

3

3

3

3

3

3.5

3

3

linear or non-linear balanced

% FL

load and at input THVD

2%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Duration of progressive power

sec

 

 

10 seconds to reach full rated current

 

 

walk-in

 

 

(selectable 5 through 30 seconds in 5 second intervals)

 

 

 

 

 

1.Rectifier operates at any of the rated supply voltages and frequencies without further adjustment.

2.At 305V input mains, the UPS maintains the specified output voltage at rated load without discharging a previously charged battery.

3.EN 50091-3: at rated load and input voltage 400V, battery charged

4.EN 50091-3: at rated load and input voltage 400V, battery charging at maximum rated power.

116

Page 128
Image 128
Emerson 30-200kVA, 50 and 60 Hz, 400V user manual Mechanical characteristics, Rectifier AC input mains

30-200kVA, 400V, 50 and 60 Hz specifications

The Emerson 400V, 50 and 60 Hz, 30-200 kVA is a robust and versatile power solution designed for various industrial and commercial applications. This equipment delivers a reliable source of power, ensuring operational continuity and efficiency for numerous critical systems.

One of the standout features of the Emerson 400V series is its exceptional load handling capability. With a kVA range of 30 to 200, it can cater to both small-scale operations and larger enterprises, making it a flexible choice for businesses looking to scale their operations. The dual frequency capability of 50 and 60 Hz allows the system to be utilized in various geographical locations, accommodating different regional power standards.

The series is built with advanced power electronics technology, resulting in a highly efficient energy conversion process. This technology not only boosts performance but also reduces energy losses, leading to significant cost savings in operational expenditures. Moreover, the Emerson 400V solution is designed with an emphasis on minimizing harmonic distortion, ensuring that it meets stringent regulations and preserving the integrity of sensitive electronic equipment.

Another critical characteristic of the Emerson 400V series is its modular design. This allows for easy upgrades and maintenance, ensuring that businesses can adapt their power solutions as their needs evolve. The system features a user-friendly interface for monitoring and managing power loads, enhancing operational oversight.

Additionally, the Emerson 400V series emphasizes robust safety features to protect both equipment and personnel. Integrated protection mechanisms, such as overload and short-circuit protection, provide peace of mind and safeguard against potential power-related incidents.

In terms of physical design, the unit is built for durability, capable of withstanding harsh operating environments while maintaining performance integrity. The compact footprint ensures that it can fit into various spaces without sacrificing power output.

Overall, the Emerson 400V, 50 and 60 Hz, 30-200 kVA system represents a comprehensive power solution that combines high efficiency, adaptability, and advanced technology, making it an ideal choice for organizations aiming for reliable power management and operational excellence.