Emerson 30-200kVA, 400V Efficiency, AC/AC, Mechanical characteristics, Rectifier AC input mains

Models: 30-200kVA 400V 50 and 60 Hz

1 132
Download 132 pages 10.43 Kb
Page 128
Image 128
Table 34 Efficiency, AC/AC

Technical Specifications

Table 34 Efficiency, AC/AC

Input and output voltage 400VAC, battery charged, full rated linear load

 

Unit of

 

 

 

 

 

 

 

 

 

Rated Power, kVA

Measurement

30

40

60

80

100

120

140

160

200

Normal Mode

%

89

90

91

91

90.6

91.1

92.5

92.7

92.8

(dual conversion)

 

 

 

 

 

 

 

 

 

 

ECO Mode

%

94

94.8

94.3

95

95

95.6

95.5

95.7

95.7

Inverter Efficiency (DC/AC) (battery at nominal voltage 480VDC and full-rated linear load)

Battery Mode

%

93

93

94

94

94

94

94

94

94

Heat Losses & Air Exchange—Ventilation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal Mode

kW

 

3.0

 

3.6

 

4.7

 

6.3

 

 

7.9

 

9.5

 

10.8

 

 

11.8

14.5

ECO Mode

kW

 

1.5

 

1.6

 

2.0

 

2.6

 

 

3.5

 

4.3

 

7.0

 

 

7.6

9.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No Load

kW

 

1.3

 

1.4

 

1.9

 

2.4

 

 

3.0

 

3.7

 

4.9

 

 

4.9

5.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Forced air cooling

L/sec

 

333

 

333

 

458

 

458

 

500

 

500

 

671

 

 

671

721

(front intake, top exhaust)

M3/hr

 

1200

 

 

 

 

1650

 

 

 

1800

 

2415

2595

Table 35 Mechanical characteristics

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated Power, kVA

Measurement

30

 

40

 

60

 

 

80

 

 

100

 

120

 

140

 

 

160

 

200

Dimensions, H x W x D

mm (in)

 

1600 x 600 x 825

 

 

 

 

1800 x 700 x 825

1800 x 1000 x 825

 

(63 x 23.6 x 32.5)

 

 

 

(70.8 x 27.5 x 32.5)

(70.8 x 39.4 x 32.5)

 

 

 

 

 

 

Mass, without batteries

kg (lb)

312

 

341

 

401

 

 

445

 

 

720

 

720

 

960

 

 

960

 

1060

(688)

 

(752)

 

(884)

 

(981)

 

(1587)

 

(1587)

 

(2116)

 

 

(2116)

 

(2337)

 

 

 

 

 

 

 

 

 

 

 

Finish

Colour

 

 

 

 

 

 

 

 

 

 

Pantone 877 (Silver grey)

 

 

 

 

 

 

 

 

 

 

eqvl Becker Silver epoxy polyester powder 041-37-2

 

 

 

 

 

 

 

 

 

 

Protection Degree

IEC 60529

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IP20

 

 

 

 

 

 

 

 

 

 

 

 

(finger-proof with front doors open or closed)

 

 

 

 

 

 

 

 

 

 

 

 

Values listed are the mass of the units with options added (ground fault sensor, bypass share inductors and redundant fans).

Table 36 Rectifier AC input (mains)

 

 

Unit of

 

 

 

 

 

 

 

 

 

Rated power, kVA

 

Measurement

30

40

60

80

100

120

140

160

200

Rated AC Input Voltage 1

 

VAC

 

 

 

380/400/415 V

 

 

 

 

 

 

 

(three-phase and sharing neutral with the bypass input)

 

Input voltage tolerance 2

 

VAC

305V to 477V 304V to 208V (output de-rated from 99% to 70%)

Frequency 1

 

Hz

 

 

50/60Hz (tolerance 40Hz to 72Hz)

 

 

Power Factor

 

 

 

 

 

 

 

 

 

 

 

full load

kW/kVA

0.99

0.99

0.99

0.99

0.99

0.99

0.99

0.99

0.99

 

 

 

 

 

 

 

 

 

 

 

half load

0.98

0.98

0.98

0.98

0.98

0.98

0.98

0.98

0.98

 

 

 

 

 

 

 

 

 

 

 

 

 

Input power

 

 

 

 

 

 

 

 

 

 

 

 

rated 3

kVA

27.2

35.9

53.3

71.0

88.8

107

122

139

174

maximum 4

32.9

43.0

64.6

85.2

107

128

159

182

228

 

Input current

 

 

 

 

 

 

 

 

 

 

 

 

rated 3

A

39

52

77

103

128

154

177

201

252

maximum 4

48

62

93

123

154

185

231

264

330

 

Harmonic Current Distort (with

THID

3

3

3

3

3

3

3.5

3

3

linear or non-linear balanced

% FL

load and at input THVD

2%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Duration of progressive power

sec

 

 

10 seconds to reach full rated current

 

 

walk-in

 

 

(selectable 5 through 30 seconds in 5 second intervals)

 

 

 

 

 

1.Rectifier operates at any of the rated supply voltages and frequencies without further adjustment.

2.At 305V input mains, the UPS maintains the specified output voltage at rated load without discharging a previously charged battery.

3.EN 50091-3: at rated load and input voltage 400V, battery charged

4.EN 50091-3: at rated load and input voltage 400V, battery charging at maximum rated power.

116

Page 128
Image 128
Emerson 30-200kVA, 400V Efficiency, AC/AC, Mechanical characteristics, Rectifier AC input mains, Technical Specifications