Emerson 30-200kVA, 50 and 60 Hz Output Dry Contacts, Emergency Power Off Input, Epo-No Epo-Nc

Models: 30-200kVA 400V 50 and 60 Hz

1 132
Download 132 pages 10.43 Kb
Page 26
Image 26
1.8.4Output Dry Contacts

Single Module UPS Installation

1.8.4Output Dry Contacts

There are three output dry contact relays at the X1 slot (see Figure 4 and Table 6)

NOTE

All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm2(16-20AWG) stranded for maximum runs between 25 and 50m (82-164 ft.) respectively.

Figure 4 Output dry contacts and EPO wiring for firmware before M162

X1

J13

 

 

J21

 

 

J25

 

 

 

 

 

 

 

BFP C

BFP S

BFP O

INV C

INV S

INV O

ACF C

ACF S

ACF O

Table 6 Output dry contact relays for firmware before M162

+12V

J25Figure 4 Output dry contacts and EPO wiring for firmware before M162

EPO-H EPO-L

X2

Position

Name

Description

J13.2

BFP_O

Bypass feedback protection relay; normally open. Closed when bypass SCR is shorted.

J13.3

BFP_S

Bypass feedback protection relay center

J13.4

BFP_C

Bypass feedback protection relay; normally closed. Open when bypass SCR is shorted.

J21.2

INV_O

Inverter mode relay; normally open. Closed when UPS is in inverter mode.

J21.3

INV_S

Inverter mode relay center

J21.4

INV_C

Inverter mode relay; normally closed. Open when UPS is in inverter mode.

J25.2

ACF_O

Main input fault relay; normally open. Closed when main input is in fault.

J25.3

ACF_S

Main input fault relay center

J25.4

ACF_C

Main input fault relay; normally closed. Open when main input is in fault.

Figure 5 EPO wiring for firmware M200 or later

J28

X2

EPO-NO EPO-NC

1.8.5Emergency Power Off Input

The UPS has an Emergency Power Off (EPO) function that operates by a button on the control panel or by a remote contact provided by the user. The EPO button is under a hinged, clear plastic shield.

The X2 slot, shown in Figure 4, is the remote EPO input interface. The EPO has an NO/NC contact point that becomes active when shorting terminals X2: 3 and 4 or open terminal connection X2: 2 and 1

If an external emergency stop facility is required, it is connected terminals X2: 1&2 or X2: 3&4 of the auxiliary terminal block (X2). It also is connected to the normally open or normally closed remote stop

14