Emerson 50 and 60 Hz, 400V, 30-200kVA Intermediate DC circuit, battery, Technical Specifications

Models: 30-200kVA 400V 50 and 60 Hz

1 132
Download 132 pages 10.43 Kb
Page 129
Image 129
Table 37 Intermediate DC circuit, battery

Technical Specifications

Table 37 Intermediate DC circuit, battery

 

Unit of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated Power, kVA

Measurement

30

 

40

 

60

 

80

100

 

120

140

 

160

 

200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery bus voltage

VDC

 

 

 

Nominal: 480V (VRLA Float charge is 540V)

 

 

 

 

 

 

 

Range: 400V ~ 600V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Quantity of lead-acid cells

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal

 

 

 

 

 

240 = [40 x 6-cell (12V) blocks]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum

 

 

 

 

 

252 = [42 x 6-cell (12V) blocks]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum

 

 

 

 

 

228 = [38 x 6-cell (12V) blocks]

 

 

 

 

 

 

 

 

 

 

 

 

 

Float Voltage (VRLA)

V/cell

 

 

 

 

2.25 V/cell (selectable from 2.2 –2.3V/cell)

 

 

 

 

 

Constant current and constant voltage (IU) charge mode

 

 

 

 

 

 

Temperature

mV/°C/cl

- 3.0 (selectable 0 to – 5.0 around 25°C [77°F] or 20°C [68°F]or inhibit)

compensation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ripple Voltage

% V float

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ripple Current 1

% C

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Boost Voltage (VRLA)

V/cell

 

 

 

2.35 V/cell (selectable from 2.30-2.40V/cell)

 

 

 

 

 

Constant current and constant voltage (IU) charge mode

 

 

 

 

 

 

 

 

 

- float-boost current trigger 0.050 C10 (selectable 0.030-0.070)

 

Boost Control

- boost-float current trigger 0.010 C10

(selectable 0.005-0.025) with

 

 

 

 

 

 

24 hr safety time-out (selectable 8-30 hr)

 

 

 

 

 

 

 

 

 

- boost mode inhibit also selectable

 

 

 

 

 

 

 

 

1.63 V/cell (selectable from 1.60~1.75 V/cell

 

End Of Discharge (VRLA)

V/cell

 

 

Auto Inverse EOD voltage x discharge current mode

 

 

 

(The end of discharge voltage increases at low discharge currents).

 

 

 

 

 

 

2.4 V/cell (selectable from 2.3-2.4V/cell)

 

 

 

Battery Charge

V/cell

 

 

Constant current and constant voltage (IU) charge mode

 

 

 

 

 

Programmable auto trigger or inhibit of boost mode

 

Battery Charging Power 2

kW

5.1

 

6.7

 

10

 

13

17

 

20

23.8

 

27.2

 

34

Max Current

A

13

 

17

 

25

 

33

43

 

50

60

 

68

 

85

(Adjustable) 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.For a battery capacity of 24Ah or that corresponding to a rated back-up time of 10 minutes, whichever is greatest.

2.At low input voltage the UPS recharge capability increases with load decrease (up to the maximum capacity indicated).

3.Maximum currents listed are for end of discharge voltage of 1.67 V/cell for 240 cells.

117

Page 129
Image 129
Emerson 50 and 60 Hz, 400V, 30-200kVA user manual Intermediate DC circuit, battery, Technical Specifications