1.6Power Cables

Single Module UPS Installation

1.6Power Cables

The cable design must comply with the voltages and currents provided in this section, follow local wir- ing practices and take into consideration the environmental conditions (temperature and physical support media).

For cable entry terminal, refer to Figures 43, 48, 52 and 56.

! WARNING

Before starting the UPS, ensure that you are aware of the location and operation of the external isolators that connect the ups input/bypass supply to the mains distribution panel.

Check that these supplies are electrically isolated and post any necessary warning signs to prevent their inadvertent operation.

Table 1

Maximum steady state AC and DC currents

 

 

 

 

 

 

 

NOMINAL CURRENT: Amps

 

 

BUSBAR STUD SIZE

 

 

 

 

 

 

 

 

 

 

 

 

Input Mains

Bypass/Output

Battery at

Input/Output/

 

 

 

with full battery

 

 

 

minimum

 

 

 

 

recharge

 

at full load

Bypass

Battery

Torque

UPS

 

 

battery

 

3ph + N

 

 

3ph + N

 

Cables

RATING

 

 

 

 

voltage

Cables

Load, Nm

 

 

 

 

 

 

 

 

 

 

 

(kVA)

380V

 

400V

 

415V

380V

400V

 

415V

(400VDC)

Bolt

Ø holes

(Bolts)

(lb/ft)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

50

 

47

 

45

46

43

 

42

64

M6

7

-

5 (1.12)

40

65

 

62

 

60

61

58

 

56

85

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

97

 

92

 

88

91

86

 

83

128

M8

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

128

 

122

 

117

121

115

 

111

170

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

160

 

152

 

146

152

145

 

139

213

 

 

 

M8: 13 (2.9)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120

191

 

181

 

175

182

174

 

167

255

 

 

M10 Ø11

 

 

 

 

 

M10: 26 (5.8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

140

222

 

211

 

204

212

201

 

194

298

M10

11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

160

254

 

241

 

232

242

230

 

222

340

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200

317

 

301

 

290

303

288

 

277

426

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For terminal location – refer to 5.0 - Installation Drawings

 

 

 

 

 

Table 2

Distance from floor to connection point on the equipment

 

 

 

 

 

Minimum Distance, mm (in)

 

 

UPS

 

 

 

 

UPS 30/40 kVA

UPS 60-80 kVA

UPS 100-120 kVA

UPS 140-200 kVA

 

 

 

 

 

 

Rectifier AC Input supply

350 (13.8)

 

305 (12)

324 (12.8)

 

 

 

 

 

Bypass AC Input supply

300 (11.8)

 

250 (9.8)

310 (12.2)

 

 

 

 

 

UPS Output AC

260 (10.2)

 

250 (9.8)

310 (12.2)

 

 

 

 

 

Battery Power

1030 (40.5)

 

230 (9)

360 (14.2)

 

 

 

 

 

 

Auxiliary cables:

1320(52)

 

1500 (59)

Monitor board (U2)

 

 

 

 

 

Communications

1070(42.1)

 

1250(49.2)

 

 

 

 

 

 

 

Earth

 

350 (13.8)

 

275 (10.8)

338 (13.3)

 

 

 

 

 

 

 

! WARNING

Failure to follow adequate earthing procedures may result in electromagnetic interference or in hazards involving electric shock and fire.