Emerson 50 and 60 Hz, 400V Mimic Power Flow, Audible Alarm Buzzer, Rectifier indicator-1

Models: 30-200kVA 400V 50 and 60 Hz

1 132
Download 132 pages 10.43 Kb
Page 105
Image 105
8.1.1Mimic Power Flow

Operator Control Panel and Display

8.1.1Mimic Power Flow

The LED mounted on the mimic flow chart represent the various power paths and current UPS oper- ational status.

Table 13

Rectifier indicator—1

 

 

 

Green

 

Rectifier in Normal Operation

 

 

 

Flashing

 

Input AC Normal, but rectifier not operating

Green

 

 

Red

 

Rectifier Failed

 

 

 

Off

 

Rectifier Not operating, Input AC Not Available or out of normal range

 

 

 

Table 14

Battery indicator—2

 

 

 

Green

 

Battery Normal, but discharging and powering the load

 

 

 

Flashing

 

Battery End of Discharge pre-warning

Green

 

 

 

 

Battery abnormal (Failed, Absent or Polarity Reversed) or Battery

Red

 

Converter abnormal

 

 

(Failed, overcurrent, overtemperature)

Off

 

Battery and Converter Normal, Battery charging.

 

 

 

Table 15

Bypass indicator—3

Green

 

Load on Bypass power

 

 

 

Red

 

Bypass not available, out of normal range or Static bypass switch fault.

 

 

 

Off

 

Bypass Normal, load not on bypass

 

 

 

Table 16

Inverter indicator—4

 

 

 

Green

 

Inverter Normal and powering the load

 

 

 

Flashing

 

Inverter ON, starting up, synchronising,

Green

 

or standing by (ECO mode)

Red

 

Inverter failed

 

 

 

Off

 

Inverter not operating

 

 

 

Table 17

Load indicator—5

Green

 

UPS output ON and Normal

 

 

 

Red

 

UPS output ON and Overloaded

 

 

 

Off

 

UPS output OFF.

 

 

Table 18 Status (Alarm) indicator—6

 

 

 

Green

 

Normal Operation

 

 

 

Yellow

 

UPS Warning e.g. AC Input Failure

 

 

 

Red

 

UPS fault e.g. Fuse or Hardware failure

 

 

 

8.1.2Audible Alarm (Buzzer)

UPS activity is accompanied by the following sounds

Table 19 Audible alarm key

Single beep

Direct Access key acknowledgement

 

 

One beep

UPS Warning e.g. AC Input Failure

per second

 

Continuous

Fault e.g. Fuse or Hardware failure

beep

 

93

Page 105
Image 105
Emerson 50 and 60 Hz Mimic Power Flow, Audible Alarm Buzzer, Rectifier indicator-1, Battery indicator-2, Load indicator-5