Emerson 400V, 30-200kVA Maintenance Bypass Cabinet Interface, External Circuit-Breaker Interface

Models: 30-200kVA 400V 50 and 60 Hz

1 132
Download 132 pages 10.43 Kb
Page 25
Image 25
1.8.2Maintenance Bypass Cabinet Interface

Single Module UPS Installation

1.8.2Maintenance Bypass Cabinet Interface

J26 and J30 are the MBC interface.

Table 4 Maintenance bypass cabinet interface

Position

Name

Description

J26.1

T_IT1

Input transformer overtemperature (NC)

J26.2

AUX_I

Reserved

 

 

 

J26.3

+12V

+12V Power

 

 

 

J26.4

GND

Power Ground

 

 

 

J30.1

FUSE

Reserved

 

 

 

J30.2

F_FAN

Fan Fail Alarm (NC)

 

 

 

J30.3

T_OT1

Output Transformer Overtemperature (NC)

J30.4

AUX_O

Reserved

 

 

 

1- Must be configured by software before becoming active

NOTE

All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm2(16-20AWG) stranded for maximum runs between 25 and 50m (82-164 ft.) respectively.

1.8.3External Circuit-Breaker Interface

J10 is the interface to any external battery circuit breaker (BCB).

Table 5 External circuit-breaker interface

Position

Name

Description

J10.1

DRV

BCB Driver Signal - Output (N.O.)

 

 

 

J10.2

FB

BCB Contact State - Input (N.O.)

 

 

 

J10.3

GND

Power Ground

 

 

 

J10.4

OL

BCB On-Line - Input - This pin will become active when

BCB interface is connected. (N.O.)

 

 

NOTE

All auxiliary cables of terminal must be double insulated. Wire should be 0.5-1.5mm2

(16-20AWG) stranded for maximum runs between 25 and 50 meters (82-164ft.) respectively.

13

Page 25
Image 25
Emerson 400V Maintenance Bypass Cabinet Interface, External Circuit-Breaker Interface, External circuit-breaker interface