Emerson 30-200kVA, 50 and 60 Hz, 400V user manual UPS messages, Operator Control Panel and Display

Models: 30-200kVA 400V 50 and 60 Hz

1 132
Download 132 pages 10.43 Kb
Page 113
Image 113
Prompt to press “enter” key to acknowledge that the UPS will be disconnected from

 

 

 

 

Operator Control Panel and Display

 

Table 23

UPS messages

 

 

 

 

 

 

 

Message

 

 

Description / Suggested Action (if any)

 

Inv. turned Off Manually

 

Manual Turn Off via front panel

 

 

 

 

 

 

EPO

 

 

Emergency Power Off direct access key pressed or external command received

 

Transfer Confirm

 

Prompt to press “enter” key to acknowledge that an interrupted load transfer to

 

 

bypass will happen.

 

 

 

 

 

Transfer Cancel

 

Prompt to press “ESC” key to avoid that an interrupted load transfer to bypass will

 

 

happen.

 

 

 

 

 

Unit Off Confirm

 

Prompt to press “enter” key to acknowledge that the UPS will be disconnected from

 

 

other paralleled UPS modules.

 

 

 

 

 

System Off Confirm

 

Prompt to press “enter” key to acknowledge that the all paralleled UPS will be

 

 

disconnected from the load.

 

 

 

 

 

Fault Reset

 

 

Fault clear direct access key pressed

 

 

 

 

 

Alarm Silence

 

Silence On/Off direct access key pressed

 

 

 

 

 

 

 

 

 

Inverter failed to turn on when Inverter On direct access key was pressed. This may

 

Turn On Fail

 

 

be as a result of Invalid Operation (Maintenance bypass on) or DC bus or rectifier

 

 

 

 

not ready.

 

Alarm Reset

 

 

Fault clear or Silence On/Off direct access key pressed

 

 

 

 

 

Bypass Mode

 

Load supplied from AC input bypass supply.

 

 

 

 

 

 

Normal Mode

 

Load supplied from Inverter output through double conversion of the AC mains input

 

 

supply.

 

 

 

 

 

Battery Mode

 

Load supplied from Inverter output through double conversion of the Battery supply.

 

 

 

 

 

 

Source share mode

 

Load supplied from Inverter output through shared double conversion of the AC

 

 

mains input supply and of the Battery supply.

 

 

 

 

 

UPS Shutdown

 

UPS Shutdown, output power-down

 

Check UPS Output

 

Inverter off during normal startup (diagnostics information only)

 

Generator Connected

 

Generator active signal received. Source share mode may be activated pending

 

 

UPS settings.

 

 

 

 

 

BCB open

 

 

Battery Circuit Breaker status (open)

 

BCB closed

 

 

Battery Circuit Breaker status (closed)

 

 

 

 

 

Battery Float Charging

 

Battery status (Float charge mode)

 

 

 

 

 

Battery Boost Charging

 

Battery status (Boost charge mode)

 

 

 

 

 

Battery Discharging

 

Battery status (discharge mode)

 

Battery Period Testing

 

Automatic periodic battery maintenance discharge test (20% capacity discharge)

 

Batt. Capacity Testing

 

User initiated battery capacity discharge test (100% capacity discharge)

 

 

 

 

 

Batt. Maint. Testing

 

User initiated maintenance discharge test (20% capacity discharge)

 

 

 

 

 

UPS System Testing

 

User initiated UPS self test

 

 

 

 

 

Inverter in Setting

 

Inverter starting up and synchronising

 

Rectifier in Setting

 

Rectifier starting up and synchronising

 

MBP-T cabinet Fan Fault

 

Maintenance bypass cabinet fans fault.

 

 

 

 

 

Ext Input TX Overtemp

 

External Input Isolation Transformer Over Temperature

 

 

 

 

 

Ext Output TX Overtemp

 

External Output Isolation Transformer Over Temperature

 

 

 

 

 

Battery Room Alarm

 

Environment in Battery Room Needs Attention

 

Rotary Sw. Test Pos.

 

Rotary switch is in test position.

 

Rotary Sw. Normal Pos.

 

Rotary switch is in normal position.

 

 

 

 

 

Rotary Sw. Bypass Pos.

 

Rotary switch is in bypass position.

 

 

 

 

 

Rotary Sw. Maint. Pos.

 

Rotary switch is in maintenance position.

 

 

 

 

 

Battery Contactor Open

 

Battery Contactor Open

 

Battery Contactor Close

 

Battery Contactor Closed

 

Battery Reverse

 

Connect the battery again and check the wiring of batteries

 

 

 

 

 

 

No Battery

 

 

Check the battery and the wiring of batteries

 

 

 

 

 

101

Page 113
Image 113
Emerson 30-200kVA, 50 and 60 Hz, 400V user manual UPS messages, Operator Control Panel and Display