7.7Isolation of One Module in a Multi-Module System

Operating Procedures

7.7Isolation of One Module in a Multi-Module System

7.7.1Multi-Module Systems With External Output CB1

Figure 66 Typical 1+N system block diagram with common input supply, with separate batteries and optional output / bypass distribution panel

Supplied

 

 

by Others

 

 

Input Mains

 

Input Mains

Supply L1, L2, L3, N

 

Supply L1, L2, L3, N

Q1

 

Q1

UPS1

 

UPS2

 

 

Rectifier

Rectifier

Charger

 

Charger

Inverter

Inverter

 

Q2

Q2

 

Q3

Q3

Q5

 

Q5

L1, L2, L3, N

L1, L2, L3, N

Q1EXT

 

Q2EXT

QUPS

 

QBYP

Distribution Cabinet

To Load

1.Turn Off inverter.

2.Open External Output isolator (Q1ext or Q2ext).

The UPS enters Isolation Status automatically, parallel signaling and communication becomes masked, and output becomes inhibited.

3.Power Off unit for maintenance.

4.Power On unit.

5.Unit enters Test Mode by configuration software setting.

6.Diagonosis or testing.

7.The UPS exits Test Mode by configuration software setting. Output becomes inhabited because of Isolation Status.

8.Return all switches to the Normal position.

9.Close External Output isolator (Q1ext or Q2ext).

The UPS exits Isolation Status automatically, parallel signaling and communication recovers,