Emerson 400V, 50 and 60 Hz, 30-200kVA user manual Battery Temperature Sensor-Optional

Models: 30-200kVA 400V 50 and 60 Hz

1 132
Download 132 pages 10.43 Kb
Page 55
Image 55
2.6.1Battery Temperature Sensor—Optional

 

 

 

 

 

 

Battery Installation

 

Table 11 Battery control label description (X102)

 

 

 

 

 

 

 

 

BCBB

 

Monitor Bd

 

 

 

X-102

 

Reference

 

 

 

Ref Label

 

Label

Description

Signal status

 

1 DRV

 

DRV

Battery circuit breaker tripping

Normal: H level voltage, BCB can close

 

 

control signal from UPS

Abnormal: L level voltage, BCB trips

 

 

 

 

 

 

2

IN (AUX)

BCB-X3

FB (IN)

Bat CB auxiliary status contact

Normal: OV when BCB is closed.

 

(Open contact = CB open)

Abnormal: open when BCB is open

 

 

 

on U2 Monitor

 

 

 

 

 

 

 

 

Normal: 0V, the BCB Board is in use.

 

4

USE

board

OL =

Bat CB Board status signal

 

 

On Line

(GND = OV from BCB Bd)

Abnormal:. open, the BCB Board is not

 

 

 

 

in use.

 

 

 

 

 

 

 

3 GND1

 

GND

GND1

GND1 to GND on U2 board

 

 

 

 

 

 

 

 

 

 

 

 

+12V Power supply from

 

 

5

(1) +12V

 

P12

Monitor Bd to Temp Monitoring

Power available: 3W.

 

 

 

X7

 

Probe & Buffer

 

 

 

 

on U2 Monitor

 

 

 

 

6

(3) 0V

GND2

GND2

GND2 to GND on U2 board

 

 

 

board

 

 

 

 

7

(2) Out

 

OUT

Buffered Bat temp Probe signal

 

 

 

from BCB Bd to Monitor Bd

 

 

 

 

 

 

 

1.Cables connected to X3 BCB must be segregated from power circuits, double insulated and of a typical 0.5 to 1mm2 cross section area for maximum runs between 25 and 50 meters respectively.

2.Battery temperature sensing cables must be less than 10 m long.

3.30 and 40kVA UPS models fitted with internal battery and any UPS models fitted with Battery Start kit contain an internal UPS battery contactor for automatic connection and disconnection of the batteries and the battery circuit breaker undervoltage coil is not used. Refer to 2.5 - Battery Control for details.

! CAUTION

Leave terminals open if the corresponding facility is not used. The commissioning engineer must program the UPS accordingly (e.g., disable battery temperature compensation, enable internal battery contactor)

2.6.1Battery Temperature Sensor—Optional

The optional external battery temperature sensor kit, supplied separately from the battery circuit breaker, contains one probe and one temperature transport board as illustrated in Figure 26. It is connected to the UPS Monitor Board (either directly or in case of multiple sensors, through the bat- tery circuit breaker board - see Figures 26 and 27).

Figure 26 Single temperature sensor and monitor board—U2

Name: W2 L = 30m

 

 

Temperature

 

 

Sensor

 

 

 

 

 

+

NC

 

 

12V

 

 

IN

 

 

-

OUT

 

 

 

GND

 

 

 

TMP-2

 

 

 

 

 

 

 

 

 

Monitor

X7

Board

– U2

 

-12V BAT-T GND

UPS

Cable W2 is packed with the temperature sensor.

43

Page 55
Image 55
Emerson 400V, 50 and 60 Hz, 30-200kVA user manual Battery Temperature Sensor-Optional