Figure 72 Battery Start Option for UPS with external battery

Options—For Assembly Inside the UPS Cabinet

Figure 72 Battery Start Option for UPS with external battery

Blue

Green

Red

1 GND

2 IN

3 P12

TMP-2

Temperature

Transport

GND4

OUT

3

 

P12

2

 

OT6-4 LM35

+

Batt-P

Contactor

Auxiliary Contact

Main Contact

Contactor

Control Coil

J12-33

J12-34

Battery +

Batt-P

J15-1

J15-2

X7

 

 

2

3

4

Monitor Board

-U2

Batt-N

-

Battery

Cabinet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Detection Board

 

Soft-In

 

 

Soft-Out

 

 

 

-M4

 

 

 

 

 

 

 

 

 

Battery Black-Start

 

Black-Start Resistor

 

 

 

 

 

Board

 

 

 

 

1 2

-1

-2

P-Bus

 

 

P-Bus

 

 

 

 

 

X2- X2-

X1

X1

N-Line

 

 

N-Line

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P

 

N

 

 

 

 

 

C

 

 

 

 

NO

 

Black-Start LED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

Manual Press-Button

 

AL6-M

 

 

 

UPS

 

 

 

 

 

 

(AB6M)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Batt-N

NOTE

Battery contactor opens after Inverter shutdown at end of battery discharge. Battery Start settings disable the end of discharge trip command to external battery circuit breaker.

9.1.5Bypass Current Sharing Inductors

Applicable in paralleled UPS configurations to ensure that the (passive) static bypass switches, when activated, share the load current. The inductors provide droop type current compensation for the oth- erwise inherent current dispersion due to SCR and cable impedance differences.

Table 26 Bypass current sharing inductors-dimensions, values

 

Dimensions

Inductor

UPS

WxLxH, mm (in)

Value (uH)

 

 

 

30/ 40 kVA

70x100x140

122

(2.8x3.9x5.5)

 

 

60/80 kVA

140x100x200

65

(5.5x3.9x7.9)

 

 

100/120kVA

210x100x250

40

(8.3x3.9x9.8)

 

 

140/160kVA

160x190x240

26

(6.3x7.5x9.4)

 

 

200kVA

160x190x240

22

(6.3x7.5x9.4)

 

 

Three bypass current sharing inductors are assembled within each UPS cabinet without requirement of additional footprint. The resulting degree of unbalance is typically less than 20% of the rated sys- tem current depending on the external cable configuration. Cable lengths from the Bypass supply to each UPS module and from the UPS module output to the paralleling point should be kept as identi- cal as possible.