Emerson 400V, 50 and 60 Hz, 30-200kVA Inverter output to critical load, Technical Specifications

Models: 30-200kVA 400V 50 and 60 Hz

1 132
Download 132 pages 10.43 Kb
Page 130
Image 130
Table 38 Inverter output to critical load

Technical Specifications

Table 38 Inverter output to critical load

Rated Power

kVA

30

40

60

 

80

 

100

 

120

140

160

200

(load pf 0.8 lag)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(load pf unity)

kW

24

32

48

 

64

 

80

 

96

112

128

160

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(load pf 0.9 lead)

kVA

24

32

48

 

64

 

80

 

96

112

128

160

Rated AC Voltage 1

V (ac)

 

 

 

 

 

 

380/400/415 V

 

 

 

 

 

(three-phase, four-wire with neutral referenced to the bypass neutral)

Frequency 2

Hz

 

 

 

 

 

50 / 60

 

 

 

 

 

 

 

 

 

 

 

110% for 60 min

 

 

 

Overload

% rated

 

 

 

 

 

125% for 10 min

 

 

 

 

 

 

 

 

 

150% for 1 min

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

225% for 200 msec

 

 

 

 

 

 

 

 

 

 

Fault Current

% rated

 

 

320% current limitation for 200 msec

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Non linear load capability 4

% rated

 

 

 

 

 

100%

 

 

 

 

Neutral current capability

% rated

 

 

 

170%

 

 

 

 

152%

135%

 

 

 

 

 

 

 

 

 

 

 

Steady state voltage stability 5

%

 

 

 

 

 

± 1 (balanced load),

 

 

 

 

 

 

 

± 2 (100% unbalanced load),

 

 

 

 

 

 

 

 

 

 

Transient voltage response 6

%

 

 

 

 

 

± 5

 

 

 

 

 

 

 

 

 

 

 

< 1 (linear load)

 

 

 

Total Harmonic Voltage Distortion

%

 

 

 

 

<3.5 (non linear load, 380V)

 

 

(THDV) 4

 

 

 

 

<4.0 (non linear load, 400V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

< 4.5 (non linear load, 415V)

 

 

 

 

 

 

 

Synchronisation - Window

Hz

 

Rated frequency ± 2 Hz (selectable ± 0.5 to ± 3Hz)

 

- Slew Rate (Max change rate of

Hz/sec

 

 

 

 

 

 

1 Hz/sec

 

 

 

synch frequency)

selectable 0.1 to 3Hz/s (single UPS), 0.2Hz/sec (paralleled.UPS)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inverter Voltage Tolerance

%V

 

 

 

 

 

± 5

 

 

 

 

(AC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Factory set to 400V – 380 or 415V selectable by commissioning engineer.

2.Factory set to 50Hz; 60 Hz selectable by commissioning engineer. Frequency converter operation also selectable.

3.EN 50091-3 (1.4.50).

4.Crest factor > 3:1 limited by IEC 62040-3 definition of non linear load.

5.EN 50091-3 (4.3.4).

6.EN 50091-3 (4.3.7) also for 0-100-0% load transient. Transient recovery time: return to within 5% of steady state output voltage within half a cycle.

118

Page 130
Image 130
Emerson 400V, 50 and 60 Hz, 30-200kVA user manual Inverter output to critical load, Technical Specifications