Operator Control Panel and Display

Current Record Window

Keeps a log the events that resulted in the current mode of operation. Ignores transient conditions that have been resolved.

Use “page” (F1) and up / down arrow to read the events.

For a complete history log, refer to the Records tab of the Menu and Data Window. Refer to Table 23 for a complete list of supported status messages.

8.2All Status and Event Messages Displayed on the UPS Front Panel

This is the complete list of UPS events and status messages supported for display in either the Record window (Historic data) or in the Current window (Prevailing data) as described in 8.1.4 - LCD Moni- tor and Menu keys.

Table 23

UPS messages

 

 

 

 

 

Message

 

 

Description / Suggested Action (if any)

Inverter Comm. Fail

 

Internal RS485 communication failure between monitor and inverter

Rectifier Comm. Fail

 

Internal RS485 communication failure between monitor and rectifier

 

 

 

 

 

 

 

The CAN communication between different UPSs within a parallel system fails.

Parallel Comm. Fail

 

1.Check if there are some UPSs not powered on in the parallel system. If so, power

 

on these UPSs and check if the alarm disappears.

 

 

 

 

 

 

2. Press Fault Clear push button.

 

 

 

Battery Overtemp.

 

The Battery temperature is over limit. Check the battery temperature and ventilation

 

 

 

Ambient Overtemp.

 

The Ambient temperature is over limit. Check the ventilation of UPS room.

Battery Fault

 

Battery detected faulty (Reserved)

Replace Battery

 

Battery test failed, Battery should be replaced.

 

 

 

 

 

 

 

Before the end of discharge, battery undervoltage pre-warning should occur. After

Battery Low Pre-warning

 

this pre-warning, battery should have the capacity for 3 minutes discharging with full

 

load. The time is user-configured from 3 to 60 minutes.

 

 

 

 

 

 

Shut down the load in time.

 

 

 

 

Battery End of Discharge

 

Inverter turned off due to low battery voltage. Check the utility failure and try to

 

recover it.

 

 

 

Mains Volt. Abnormal

 

Mains Voltage exceeds the upper or lower limit and results in rectifier shutdown.

 

Check the input line-to-neutral voltage amplitude of rectifier.

 

 

 

Mains Undervoltage

 

Mains Voltage is undervoltage with derated load.

 

Check the input line-to-line voltage amplitude of rectifier

 

 

 

Mains Freq. Abnormal

 

Mains frequency is out of limit range and results in rectifier shutdown.

 

Check the rectifier’s input voltage frequency

 

 

 

Rectifier Fault

 

Rectifier detected faulty. Rectifier shuts down. Battery discharges.

Rectifier Overtemp.

 

The temperature of heat sink is too high to keep the rectifier running.

 

The UPS can recover automatically. Check the environment and ventilation.

 

 

 

Batt. Contactor Fail

 

Battery contactor or circuit breaker not responding to control signals.

Batt. Charger Fault

 

The voltage of the battery charger is too high.

 

 

 

Control Power 1 Fail

 

UPS operates but Redundant Control Power is not available.

 

 

 

Mains Phase Reversed

 

AC Input phase sequence is reversed.

 

 

 

Rectifier Overcurrent

 

Rectifier is overloaded.

Soft Start Fail

 

Rectifier could not start due to low DC bus voltage

98

Page 110
Image 110
Emerson 30-200kVA, 50 and 60 Hz, 400V Current Record Window, UPS messages, Message Description / Suggested Action if any

30-200kVA, 400V, 50 and 60 Hz specifications

The Emerson 400V, 50 and 60 Hz, 30-200 kVA is a robust and versatile power solution designed for various industrial and commercial applications. This equipment delivers a reliable source of power, ensuring operational continuity and efficiency for numerous critical systems.

One of the standout features of the Emerson 400V series is its exceptional load handling capability. With a kVA range of 30 to 200, it can cater to both small-scale operations and larger enterprises, making it a flexible choice for businesses looking to scale their operations. The dual frequency capability of 50 and 60 Hz allows the system to be utilized in various geographical locations, accommodating different regional power standards.

The series is built with advanced power electronics technology, resulting in a highly efficient energy conversion process. This technology not only boosts performance but also reduces energy losses, leading to significant cost savings in operational expenditures. Moreover, the Emerson 400V solution is designed with an emphasis on minimizing harmonic distortion, ensuring that it meets stringent regulations and preserving the integrity of sensitive electronic equipment.

Another critical characteristic of the Emerson 400V series is its modular design. This allows for easy upgrades and maintenance, ensuring that businesses can adapt their power solutions as their needs evolve. The system features a user-friendly interface for monitoring and managing power loads, enhancing operational oversight.

Additionally, the Emerson 400V series emphasizes robust safety features to protect both equipment and personnel. Integrated protection mechanisms, such as overload and short-circuit protection, provide peace of mind and safeguard against potential power-related incidents.

In terms of physical design, the unit is built for durability, capable of withstanding harsh operating environments while maintaining performance integrity. The compact footprint ensures that it can fit into various spaces without sacrificing power output.

Overall, the Emerson 400V, 50 and 60 Hz, 30-200 kVA system represents a comprehensive power solution that combines high efficiency, adaptability, and advanced technology, making it an ideal choice for organizations aiming for reliable power management and operational excellence.