Emerson 400V Rectifier and Bypass Input, Earth Leakage RCD, External Battery, UPS Output

Models: 30-200kVA 400V 50 and 60 Hz

1 132
Download 132 pages 10.43 Kb
Page 19
Image 19
1.5.1Rectifier and Bypass Input

Single Module UPS Installation

1.5.1Rectifier and Bypass Input

Overcurrent protection must be installed at the distribution panel of the incoming main supply. The protection must discriminate with the power cables current capacity and with the overload capacity of the system (see Table 38). As a guideline, a thermomagnetic circuit breaker, with an IEC 60947-2 trip curve C (normal) for 125% of the current listed in Table 1 is suitable.

Split-Bypass—If a split-bypass is used, install separate protective devices for the rectifier and for the bypass in the incoming mains distribution panel.

NOTE

Rectifier and bypass input sources must be referenced to the same neutral potential.

NOTE

For IT power systems, four-pole protective devices must be used, external to the UPS, both upstream of the input distribution panel and downstream (toward the load).

Earth Leakage (RCD)

Any residual current detector (RCD) installed upstream of the UPS input supply must be:

sensitive to DC unidirectional pulses (Class A)

insensitive to transient current pulses, and

must have an average sensitivity, adjustable between 0.3 and 1A.

Figure 1 Residual current circuit breakers (RCCB) symbols

To avoid false alarms, earth leakage monitoring devices when used in systems with split-bypass input or when used in paralleled UPS configurations, must be located upstream of the common neutral sinking point. Alternatively, the device must monitor the combined four-wire rectifier and split- bypass input currents.

The residual earth current introduced by the RFI suppression filter inside the UPS is greater than 3.5mA, 1000mA for 30-80kVA, 2000mA for 100-120kVA models and less than 2500mA for

140-200kVA models. Liebert recommends verifying the selectivity with all other differential devices both upstream of the input distribution board and downstream (toward the load).

1.5.2External Battery

The UPS and its associated batteries are protected against overcurrents through a DC compatible dis- connect device.

1.5.3UPS Output

Any external distribution board used for load distribution shall be fitted with protective devices that discriminate with those used at the bypass input to the UPS and with the UPS overload characteris- tics (see Table 38).

7

Page 19
Image 19
Emerson 400V, 50 and 60 Hz, 30-200kVA user manual Rectifier and Bypass Input, Earth Leakage RCD, External Battery, UPS Output