Emerson B-106-300NH instruction manual Jumpers on HPS Mother Board

Models: B-106-300NH

1 182
Download 182 pages 23.73 Kb
Page 53
Image 53

World Class 3000

Instruction Manual

IB-106-300NH Rev. 4.2 July 2002

2

1

2

NOTES:

 

1

100 V.A.C. OPERATION REQUIRES TRANSFORMER PART

 

 

NUMBER 1M02961G02.

 

2

REFER TO TABLE 3-5 FOR PROPER SET POINT SELECTION.

0310122

 

 

Figure 2-16. Jumper Selection Label

NOTE

Before supplying power to the heater power supply, verify that jumpers JM3, JM6 are removed and JM7 is installed. If relay wire (Figure 2-14,note 1) is in- stalled, JM2 must be removed from HPS Mother Board (Figure 2-17).

4.Before supplying power to the heater power supply, verify that the jumpers on the mother board, Figure 2-17,are properly configured. Jumpers JM3 and JM6 should be removed and JM7 should be installed.

Additionally, make sure that the proper jumper for your line voltage is installed, Figure 2-16.If relay wire (Figure 2-14,note 1) is not installed, JM 2 should be installed on the HPS Mother Board (Figure 2-17).

NOTE

Refer to Figure 2-9and Figure 2-11for proper IFT jumper configuration. IFT microprocessor and interconnect board jumper configurations must be set correctly in order for HPS to work properly.

FUSES

JM1

JM2

JM4

JM7

JM5

3D3 080G REV

FUSE

NOTE: ALL FUSES ARE 5A @ 250 VAC,

ANTI-SURGE, CASE SIZE

5 X 20 MM, TYPE T TO IEC127,

SCHURTER.29850001

Figure 2-17. Jumpers on HPS Mother Board

Rosemount Analytical Inc. A Division of Emerson Process Management

Installation 2-21

Page 53
Image 53
Emerson B-106-300NH instruction manual Jumpers on HPS Mother Board