Emerson B-106-300NH Output Jumper, Analog Output, Condition during Microcontroller failure Jumper

Models: B-106-300NH

1 182
Download 182 pages 23.73 Kb
Page 46
Image 46

Instruction Manual

IB-106-300NH Rev. 4.2 July 2002

World Class 3000

OUTPUT

JUMPER

 

 

HPS

Remove JM6

Probe (No HPS)

Install JM6

 

 

 

 

ANALOG OUTPUT

 

(Condition during

 

microcontroller failure)

Jumper

Output = zero

Install JM7

Output = maximum

Remove JM7

 

 

chart recorders. Relay outputs are typi- cally sent to annunciators.

3.Relays K1 and K2 are user configur- able from the probe SETUP sub-menu (Table 5-5). Typically these are used to indicate O2 values above or below specified tolerances. OK relay is ener- gized when unit is functioning properly.

4.All wiring must conform to local and national codes.

(See Figure 2-10for jumper locations.)

Figure 2-9. Microprocessor Board

Jumper Configuration

c.Analog Output and Relay Output Connections

5.Connect the analog output and relay outputs as shown in Figure 2-12.

2-3 HEATER POWER SUPPLY INSTALLATION

a. Mechanical Installation

1.The microprocessor board has a se- lector for voltage or current operations. Figure 2-10shows switch orientation. In voltage mode, output is 0-10 V. In the current mode, the output can be configured from the SETUP menu to be 0-20 mA or 4-20 mA.

2.The analog output and relay outputs are programmed by the user as needed. The analog output is typically sent to recording equipment such as

The outline drawing of the heater power supply enclosure in Figure 2-13shows mounting centers and clearances. The NEMA 4X enclosure is designed to be mounted on a wall or bulkhead. The heater power supply should be installed no further than 150 feet (45 m) from the probe. The heater power supply must be located in a location free from significant ambient tem- perature changes and electrical noise. Am- bient temperature must be between -20° and 140°F (-30° and 60°C).

2-14 Installation

Rosemount Analytical Inc. A Division of Emerson Process Management

Page 46
Image 46
Emerson B-106-300NH instruction manual Output Jumper, Analog Output, Condition during Microcontroller failure Jumper