Emerson PMC-CGM manual

Models: PMC-CGM

1 66
Download 66 pages 1.17 Kb
Page 55
Image 55

cgmSys

MIB Description

 

 

Table 5-5 cgmControl Elements (continued)

OID

MIB Object

Description

Access

 

 

 

 

.1.1.41

cgmCLK2OutputFrequency

The output frequency of CLK2:

r/w

 

 

0

- CLK2 output disabled

 

 

 

1

- 19.44 MHz

 

 

 

Default value is (1).

 

 

 

 

 

.1.1.42

cgmCLK3OutputFrequency

Not supported on PMC-CGM

r/w

 

 

 

 

.1.1.43

cgmCLK1OutputFramePulse

The output frame pulse of the T1 clock:

r/w

 

 

0

- Not inverted, not pulsed

 

 

 

1

- Not inverted, pulsed

 

 

 

2

- Inverted, not pulsed

 

 

 

3

- Inverted, pulsed

 

 

 

Default value is (0).

 

 

 

 

 

.1.1.44

cgmT4ClkSquelch

When set to 0 (enable) the output of the T4 PLL

 

 

 

is squelched if no valid input is selected.

 

 

 

If set to 1 (disable) an output is provided in any

 

 

 

case.

 

 

 

 

 

 

5.3cgmSys

The cgmSys branch contains the following information:

zcgmEventTable - for details refer to Table 5-6 on page 55.

zVarious MIB objects that are described in Table 5-8 on page 58.

For a description on how to use these objects refer to Configure Parameters for Event Handling on page 44, Perform Firmware/Software Upgrade on page 42.

The cgmEventTable (OID:.1.3.6.1.4.1.3656.8152.1.3.1) uses cgmEventNumber as index. The elements of the trap definiton cgmLogEvent (OID:.1.3.6.1.4.1.3656.8152.1.2.0.1) is identical to the elements defined in cgmEventTable.

Table 5-6 cgmEventTable

 

OID

MIB Object

Description

Access

 

 

 

 

 

 

.1.3.1.1.2

cgmEventTime

System time stamp when event occurred (this is the

r

 

 

 

module's run-time since power-up).

 

 

 

 

 

 

 

.1.3.1.1.3

cgmEventSeverity

The event's severity level

r

 

 

 

1.

Critical (0): An error has occurred which needs

 

 

 

 

immediate attention.

 

 

 

 

2.

Warnings (1): An error has occurred which may affect

 

 

 

 

board operation but does not require immediate attention.

 

 

 

 

3.

Events (2): An event occurred in a board subsystem

 

 

 

 

which may need attention (e.g. the PLL gained lock).

 

 

 

 

4.

Information (3): Various information messages helpful

 

 

 

 

for troubleshooting or monitoring the state of the CGM

 

 

 

 

module.

 

 

 

 

 

 

 

 

 

 

 

 

 

PMC-CGM Installation and Use (6806800D53C)

 

55

Page 55
Image 55
Emerson PMC-CGM manual