Failure to remove the Xi from automatic control loops prior to performing this procedure may result in a dangerous operating condition.

 

7. In the first O2 CAL screen, a "Loop should be removed from automatic

 

control" warning appears. Remove the Xi from any automatic control

 

loop to avoid a potentially dangerous operating condition and press OK.

 

8. Follow the handheld 375/475 Field Communicator display prompts to

 

perform the O2 cal procedure.

D/A TRIM

The D/A trim procedure is used to calibrate the 4-20 mA output signal to a

 

precision mA measurement device.

 

The two paragraphs that follow describe how to perform a D/A trim for two of

 

the three basic system configurations shown in Figure 4-10. Only the signal to

 

the DCS needs to be trimmed.

Figure 4-6. D/A Trim Methods,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Simplified

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D/A Trim with Xi

For systems with configuration 1, shown in Figure 4-6, use the handheld

 

375/475 Field Communicator to access the D/A trim procedure according to

 

the instructions that follow. Refer to the 375/475 Field Communicator Xi Menu

 

Tree in Figure 4-2.

1. From the DEVICE SETUP screen select menu item 2, DIAG/SERVICE, to access the diagnostics and service menu options.

2. Select menu item 3, CALIBRATION, to access the calibration menu options.

3. Select menu item 3, 4-20 mA SIG, to access the 4-20 mA SIGNAL screen.

4. Select menu item 1, D/A Trim, to start the trim procedure.

4-16

Page 54
Image 54
Emerson Process Management IM-106-910Xi instruction manual Trim with