Xi Advanced Electronics
Instruction Manual
IM-106-910Xi, Original Issue November 2010
Failure to remove the Xi from automatic control loops prior to performing this procedure may result in a dangerous operating condition.
| 7. In the first O2 CAL screen, a "Loop should be removed from automatic | ||||||||||||||||||||||||||
| control" warning appears. Remove the Xi from any automatic control | ||||||||||||||||||||||||||
| loop to avoid a potentially dangerous operating condition and press OK. | ||||||||||||||||||||||||||
| 8. Follow the handheld 375/475 Field Communicator display prompts to | ||||||||||||||||||||||||||
| perform the O2 cal procedure. | ||||||||||||||||||||||||||
D/A TRIM | The D/A trim procedure is used to calibrate the | ||||||||||||||||||||||||||
| precision mA measurement device. | ||||||||||||||||||||||||||
| The two paragraphs that follow describe how to perform a D/A trim for two of | ||||||||||||||||||||||||||
| the three basic system configurations shown in Figure | ||||||||||||||||||||||||||
| the DCS needs to be trimmed. | ||||||||||||||||||||||||||
Figure |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Simplified |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
D/A Trim with Xi | For systems with configuration 1, shown in Figure |
| 375/475 Field Communicator to access the D/A trim procedure according to |
| the instructions that follow. Refer to the 375/475 Field Communicator Xi Menu |
| Tree in Figure |
1. From the DEVICE SETUP screen select menu item 2, DIAG/SERVICE, to access the diagnostics and service menu options.
2. Select menu item 3, CALIBRATION, to access the calibration menu options.
3. Select menu item 3,
4. Select menu item 1, D/A Trim, to start the trim procedure.